Reference Manual
00809-0100-4530, Rev DD
May 2016
For clean liquids, use a coaxial probe to reduce effect of potential electrical disturbances.
Figure 3-5. Coaxial Probe in an Open-Air Application
For optimal single lead probe performance in non-metallic tanks, the probe must be
mounted with a metal flange, or screwed in to a metal sheet (d > 14 in./350 mm) if a
threaded version is used.
Figure 3-6. Mounting in Non-Metallic Tanks
3.2.3
Installation in concrete silos
Figure 3-7. Installation in Concrete Silos
Metal flange
Metal sheet
(d > 14 in./350 mm)
Metal