![Rosemount 5300 Series Скачать руководство пользователя страница 368](http://html1.mh-extra.com/html/rosemount/5300-series/5300-series_reference-manual_1487396368.webp)
May 2016
Reference Manual
00809-0100-4530, Rev DD
354
BLOCK_ALM
36
The block alarm is used for all configuration, hardware, connection failure or
system problems in the block. The cause of the alert is entered in the subcode
field. The first alert to become active will set the Active status in the Status
parameter. As soon as the Unreported status is cleared by the alert reporting
task, another block alert may be reported without clearing the Active status, if
the subcode has changed.
BLOCK_ERR
06
This parameter reflects the error status associated with the hardware or
software components associated with a block. It is a bit string, so that multiple
errors may be shown.
CLR_FSTATE
30
Writing a Clear to this parameter will clear the device FAIL_SAFE if the field
condition has cleared.
CONFIRM_TIME
33
The time the resource will wait for confirmation of receipt of a report before
trying again. Retry will not happen when CONFIRM_TIME=0.
CYCLE_SEL
20
Used to select the block execution method for this resource. The Rosemount
5300 supports the following:
Scheduled: Blocks are only executed based on the function block schedule.
Block Execution: A block may be executed by linking to another blocks
completion.
CYCLE_TYPE
19
Identifies the block execution methods available for this resource.
DD_RESOURCE
09
String identifying the tag of the resource which contains the Device
Description for this resource.
DD_REV
13
Revision of the DD associated with the resource - used by an interface device to
locate the DD file for the resource.
DEFINE_WRITE_LOCK
60
Allows the operator to select how WRITE_LOCK behaves. The initial value is
“lock everything”. If the value is set to “lock only physical device” then the
resource and transducer blocks of the device will be locked but changes to
function blocks will be allowed.
DETAILED_STATUS
55
Indicates the state of the transmitter. See Resource Block detailed status
codes.
DEV_REV
12
Manufacturer revision number associated with the resource - used by an
interface device to locate the DD file for the resource.
DEV_STRING
43
This is used to load new licensing into the device. The value can be written but
will always read back with a value of 0.
DEV_TYPE
11
Manufacturer’s model number associated with the resource - used by interface
devices to locate the DD file for the resource.
DIAG_OPTION
46
Indicates which diagnostics licensing options are enabled.
DISTRIBUTOR
42
Reserved for use as distributor ID. No Foundation enumerations defined at this
time.
DOWNLOAD_MODE
67
Gives access to the boot block code for over-the-wire downloads.
0 = Uninitialized
1 = Run mode
2 = Download mode
FAULT_STATE
28
Condition set by loss of communication to an output block, fault promoted to
an output block or physical contact. When FAIL_SAFE condition is set, then
output function blocks will perform their FAIL_SAFE actions.
FAILED_ACTIVE
72
Enumerated list of failure conditions within a device.
FAILED_ALM
73
Alarm indicating a failure within a device which makes the device non-opera-
tional.
Parameter
Index number Description
Содержание 5300 Series
Страница 2: ......
Страница 12: ...Reference Manual 00809 0100 4530 Rev DD Contents May 2016 xii Contents ...
Страница 94: ...80 Reference Manual 00809 0100 4530 Rev DD Electrical Installation May 2016 Electrical Installation ...
Страница 162: ...148 Reference Manual 00809 0100 4530 Rev DD Operation May 2016 Operation ...
Страница 214: ...200 Reference Manual 00809 0100 4530 Rev DD Service and Troubleshooting May 2016 Service and Troubleshooting ...
Страница 310: ...Product Certifications May 2016 Reference Manual 00809 0100 4530 Rev DD 296 Product Certifications ...
Страница 358: ...Level Transducer Block May 2016 Reference Manual 00809 0100 4530 Rev DD 344 Level Transducer Block ...
Страница 431: ...5 Reference Manual 00809 0100 4530 Rev DD May 2016 ...