L_TYPE
16
None
Linearization type. Determines whether the field value is
used directly (Direct) or is converted linearly (Indirect).
LO_ALM
35
None
The LO alarm data, which includes a value of the alarm, a
timestamp of occurrence and the state of the alarm.
LO_LIM
30
EU of PV_SCALE
The setting for the alarm limit used to detect the LO alarm
condition.
LO_LO_ALM
36
None
The LO LO alarm data, which includes a value of the alarm, a
timestamp of occurrence and the state of the alarm.
LO_LO_LIM
32
EU of PV_SCALE
The setting for the alarm limit used to detect the LO LO alarm
condition.
LO_LO_PRI
31
None
The priority of the LO LO alarm.
LO_PRI
29
None
The priority of the LO alarm.
LOW_CUT
17
%
If percentage value of transducer input fails below this, PV =
0.
MODE_BLK
05
None
The actual, target, permitted, and normal modes of the
block.
Target: The mode to “go to”
Actual: The mode the “block is currently in”
Permitted: Allowed modes that target may take on
Normal: Most common mode for target
OUT
08
EU of OUT_SCALE The block output value and status.
OUT_D
37
None
Discrete output to indicate a selected alarm condition.
OUT_SCALE
11
None
The high and low scale values, engineering units code, and
number of digits to the right of the decimal point associated
with OUT.
PV
07
EU of XD_SCALE
The process variable used in block execution.
PV_FTIME
18
Seconds
The time constant of the first-order PV filter. It is the time
required for a 63% change in the IN value.
SIMULATE
09
None
A group of data that contains the current transducer value
and status, the simulated transducer value and status, and
the enable/disable bit.
STRATEGY
03
None
The strategy field can be used to identify grouping of blocks.
This data is not checked or processed by the block.
ST_REV
01
None
The revision level of the static data associated with the
function block. The revision value will be incremented each
time a static parameter value in the block is changed.
TAG_DESC
02
None
The user description of the intended application of the block.
UPDATE_EVT
20
None
This alert is generated by any change to the static data.
VAR_INDEX
39
% of OUT Range
The average absolute error between the PV and its previous
mean value over that evaluation time defined by VAR_SCAN.
VAR_SCAN
40
Seconds
The time over which the VAR_INDEX is evaluated.
XD_SCALE
10
None
The high and low scale values, engineering units code, and
number of digits to the right of the decimal point associated
with the channel input value.
Parameter
Index Number Units
Description
Содержание 5300 Series
Страница 2: ......
Страница 12: ...Reference Manual 00809 0100 4530 Rev DD Contents May 2016 xii Contents ...
Страница 94: ...80 Reference Manual 00809 0100 4530 Rev DD Electrical Installation May 2016 Electrical Installation ...
Страница 162: ...148 Reference Manual 00809 0100 4530 Rev DD Operation May 2016 Operation ...
Страница 214: ...200 Reference Manual 00809 0100 4530 Rev DD Service and Troubleshooting May 2016 Service and Troubleshooting ...
Страница 310: ...Product Certifications May 2016 Reference Manual 00809 0100 4530 Rev DD 296 Product Certifications ...
Страница 358: ...Level Transducer Block May 2016 Reference Manual 00809 0100 4530 Rev DD 344 Level Transducer Block ...
Страница 431: ...5 Reference Manual 00809 0100 4530 Rev DD May 2016 ...