114
Reference Manual
00809-0100-4530, Rev DD
May 2016
Restart the device
14.
Restart the device.
When the transmitter is configured, it should be restarted to make sure that all
configuration changes are properly activated and the transmitter performs as
expected. It may take up to 60 seconds after the restart button is pressed until
measurement values are updated.
Verify level
15.
Run Verify Level.
Run the Verify Level tool to match the product level reported by the device to a
reference measurement (measured by using for example handgauging). If any
difference, the Calibration Distance parameter will be adjusted as shown in