Rosemount 5300 Series with HART® to Modbus® Converter
May 2016
Reference Manual
00809-0100-4530, Rev DD
390
Rosemount 5300 Series with HART® to Modbus® Converter
J.8.4
Levelmaster communication setup
The default and configurable parameter values can be found in
.
Table J-6. Levelmaster Communication Parameters
To reset the communication parameters to default Levelmaster settings, use the following
Modbus Message:
HMC M2
Levelmaster parameter configuration example
You want to use address 2 for the Rosemount 5300 Series Transmitter and the host uses the
following parameters:
Table J-7. Parameters Used by the Host (In Case of Levelmaster, Example)
To configure the Rosemount 5300 Series Transmitter to communicate with the host in this
example, the following text string is written to the Modbus message area.
HMC M2 A2 B9600 D7 PN S1.
Note
Include all the parameters when writing to the message area.
Note that an address must be unique on the bus.
HMC:
These three letters are used for safety and will eliminate the risk of changing the
configuration data by mistake.
M2:
This means that the Levelmaster protocol is to be used.
Parameter
Default value
Configurable value
Baud Rate
9600
1200, 2400, 4800, 9600, 19200
Start Bits
One
One
Data Bits
Seven
Seven, Eight
Parity
None
None, Odd, Even
Stop Bits
One
One or Two
Address
1
1-99
Parameter
Value
Baud Rate
9600
Start Bits
One
Data Bits
Seven
Parity
None
Stop Bits
One
Содержание 5300 Series
Страница 2: ......
Страница 12: ...Reference Manual 00809 0100 4530 Rev DD Contents May 2016 xii Contents ...
Страница 94: ...80 Reference Manual 00809 0100 4530 Rev DD Electrical Installation May 2016 Electrical Installation ...
Страница 162: ...148 Reference Manual 00809 0100 4530 Rev DD Operation May 2016 Operation ...
Страница 214: ...200 Reference Manual 00809 0100 4530 Rev DD Service and Troubleshooting May 2016 Service and Troubleshooting ...
Страница 310: ...Product Certifications May 2016 Reference Manual 00809 0100 4530 Rev DD 296 Product Certifications ...
Страница 358: ...Level Transducer Block May 2016 Reference Manual 00809 0100 4530 Rev DD 344 Level Transducer Block ...