184
Reference Manual
00809-0100-4530, Rev DD
May 2016
7.22
Diagnostic messages
7.22.1
Device status
Device status messages that may appear on the Integral Display, on the Field
Communicator, or in RMM are shown in
Table 7-4. Device Status
Message
Description
Action
Running Boot Software
The application software could not be
started.
Contact Emerson Process
Management Service Department.
Device Warning
A device warning is active.
See Warning Messages for details.
Device Error
A device error is active.
See Error Messages for details.
Sim Mode 0 Active
The simulation mode is active.
Turn off the simulation mode in RRM,
select Tools, Simulation Mode, and
click the Stop button.
Advanced Simulation Mode Active
The advanced simulation mode is active.
To turn off the Advanced Simulation
mode, set Holding Register 3600=0
(see
Interface Invalid
The interface measurement is invalid.
Check the Error Messages, Warning
Messages, and the Interface Status for
details.
Invalid Measurement
The level measurement is invalid.
Check Error Messages, Warning
Messages, and Measurement Status for
details.
User Register Area Write Protected The configuration registers are write
protected.
Use the Lock/Unlock function to turn
off the write protection (see
protecting a transmitter” on
page 174
Write Protected Jumper Set
Write protection jumper on the display is
enabled.
Remove the write protection jumper.
Factory Settings Used
The factory default configuration is used.
The transmitter has lost its calibration.
Contact Emerson Process
Management Service Department.
Probe missing
Probe is not detected.
Check that the probe is correctly
mounted. Check the connection
between probe and transmitter head.
Содержание 5300 Series
Страница 2: ......
Страница 12: ...Reference Manual 00809 0100 4530 Rev DD Contents May 2016 xii Contents ...
Страница 94: ...80 Reference Manual 00809 0100 4530 Rev DD Electrical Installation May 2016 Electrical Installation ...
Страница 162: ...148 Reference Manual 00809 0100 4530 Rev DD Operation May 2016 Operation ...
Страница 214: ...200 Reference Manual 00809 0100 4530 Rev DD Service and Troubleshooting May 2016 Service and Troubleshooting ...
Страница 310: ...Product Certifications May 2016 Reference Manual 00809 0100 4530 Rev DD 296 Product Certifications ...
Страница 358: ...Level Transducer Block May 2016 Reference Manual 00809 0100 4530 Rev DD 344 Level Transducer Block ...
Страница 431: ...5 Reference Manual 00809 0100 4530 Rev DD May 2016 ...