76
Reference Manual
00809-0100-4530, Rev DD
May 2016
4.8.2
Non-intrinsically safe output
With non-intrinsically safe power supply in non-hazardous installations or
explosion-proof/flameproof installations, wire the transmitter as shown in
.
Note
Make sure that the power supply is off when connecting the transmitter.
Figure 4-8. Wiring for Non-Intrinsically Safe Power Supply (F
OUNDATION
Fieldbus)
Note
For explosion-proof/flameproof installations, make sure the transmitter is grounded to the
internal ground terminal inside the terminal compartment in accordance with national and
local electrical codes.
Power
supply
Field Communicator
Rosemount 5300 Series
Radar Transmitter
PC
U
max
= 250 V
Fieldbus modem