May 2016
Reference Manual
00809-0100-4530, Rev DD
303
Note
Before changing the Hold Off Distance/UNZ, check entered value for the high alarm limit.
The high alarm limit must be outside the Hold Off Distance/UNZ.
To set the Hold Off Distance/Upper Null Zone with a Field Communicator:
1.
Select the HART command [2, 1, 2, 3].
2.
Select the Upper Null Zone option.
3.
Enter the desired value.
To set the Hold Off Distance/Upper Null Zone with RRM:
1.
Start RRM.
2.
Select
Setup
>
Tank
.
3.
Select the
Probe
tab.
4.
Type the desired value in the
Hold Off Distance/UNZ
field.
5.
Click
Store
. Now the Hold Off Distance/UNZ is stored in the transmitter memory.