121
Reference Manual
00809-0100-4530, Rev DD
May 2016
7.
Select the
TRANSDUCER1100
block and choose the
Geometry
tab.
8.
Tank height
is the distance from the upper reference point to the tank bottom (see
“Tank and probe geometry” on page 88
). Make sure that this number is as accurate
as possible.
9.
Select the
Mounting type
used.
10.
Select
Inner
diameter
if using pipe, chamber, or nozzle.
11.
Type
Nozzle Height
if using nozzle.
F
OUNDATION
Fieldbus parameter:
TRANSDUCER 1100 > GEOM_TANK_HEIGHT
TRANSDUCER 1100 > MOUNTING_TYPE
TRANSDUCER 1100 > PIPE_DIAMETER
TRANSDUCER 1100 > NOZZLE_HEIGHT
12.
Select the
Environment
tab.
13.
Normally, the measurement mode does not need to be changed. The transmitter is
pre-configured according to the specified model.