Rosemount 5300 Series with HART® to Modbus® Converter
May 2016
Reference Manual
00809-0100-4530, Rev DD
404
Rosemount 5300 Series with HART® to Modbus® Converter
J.11.3
ABB TotalFlow
Figure J-11. Wiring Diagram for Connecting Rosemount 5300 Modbus to ABB
TotalFlow
Table J-21. Parameter Values (In Case of ABB TotalFlow)
The Input Register Base Number needs to be added to the Input Register address of the
Rosemount 5300 Series Transmitter. In this case, register 1302 needs to have 1303 entered
as the address etc.
J.11.4
Thermo Electron Autopilot
Figure J-12. Wiring Diagram for Connecting Rosemount 5300 Modbus to Thermo
Electron Autopilot
Parameter
Value
Baud Rate
9600
Floating Point Format Code
0
RTU Data Type
16 Bit Modicon
Input Register Base Number
1
TOTALFLOW
COMM 1/2
1 VBAT
2 GND
3
4
5
6 Bus -
7
8 Bus +
9
5300 Modbus
POWER +
POWER -
MA
MB
CEB TB1
1 RX +
2 RX -
MA
MB
POWER +
POWER -
AutoPILOT
5300 Modbus
Power Supply
+ 8 to + 30 Vdc
(max. rating)
GND
Содержание 5300 Series
Страница 2: ......
Страница 12: ...Reference Manual 00809 0100 4530 Rev DD Contents May 2016 xii Contents ...
Страница 94: ...80 Reference Manual 00809 0100 4530 Rev DD Electrical Installation May 2016 Electrical Installation ...
Страница 162: ...148 Reference Manual 00809 0100 4530 Rev DD Operation May 2016 Operation ...
Страница 214: ...200 Reference Manual 00809 0100 4530 Rev DD Service and Troubleshooting May 2016 Service and Troubleshooting ...
Страница 310: ...Product Certifications May 2016 Reference Manual 00809 0100 4530 Rev DD 296 Product Certifications ...
Страница 358: ...Level Transducer Block May 2016 Reference Manual 00809 0100 4530 Rev DD 344 Level Transducer Block ...
Страница 431: ...5 Reference Manual 00809 0100 4530 Rev DD May 2016 ...