7.22.2
Errors
Error messages that may be displayed on the Integral Display, on a Field Communicator, in
AMS Device Manager, or in RRM are shown in
. Errors normally result in Analog
Output alarm.
Errors are indicated in RRM in the
Diagnostics
window.
Table 7-5. Error Messages
Message
Description
Action
RAM error
An error in the gauge data memory (RAM) has
been detected during the startup tests.
Note:
This automatically resets the gauge.
Contact Emerson Process Management
Service Department.
FPROM error
An error in the gauge program memory (FPROM)
has been detected during the startup tests.
Note:
This automatically resets the gauge.
Contact Emerson Process Management
Service Department.
Database (Hreg) error
An error in the transmitter configuration
memory (EEPROM) has been detected. The error
is either a checksum error that can be solved by
loading the default database or a hardware error.
Note:
The default values are used until the
problem is solved.
Load default database and restart the
transmitter. Contact Emerson Process
Management Service Department if the
problem persists.
Microwave Module error
An error in the microwave module.
Contact Emerson Process Management
Service Department.
LCD error
An error in the LCD is detected.
Contact Emerson Process Management
Service Department.
Modem error
An error in the modem used for digital
communication has been detected.
Contact Emerson Process Management
Service Department.
Analog out error
An error in the Analog Out Module.
Contact Emerson Process Management
Service Department.
Internal temperature error
An error in the internal temperature
measurement.
-40 ºC<Internal Temperature<85 ºC.
Contact Emerson Process Management
Service Department.
Other hardware error
An unspecified hardware error has been
detected.
Contact Emerson Process Management
Service Department.
Measurement error
A serious measurement error has been detected.
Contact Emerson Process Management
Service Department.
Configuration error
At least one configuration parameter is outside
allowed range.
Note:
The default values are used until the
problem is solved.
Load the default database and
restart the transmitter (see
to factory settings” on page 169
)
Configure the transmitter or upload
a backup configuration file (see
“Backing up the transmitter
configuration” on page 167
)
Contact Emerson Process
Management Service Department if
the problem persists
Содержание 5300 Series
Страница 2: ......
Страница 12: ...Reference Manual 00809 0100 4530 Rev DD Contents May 2016 xii Contents ...
Страница 94: ...80 Reference Manual 00809 0100 4530 Rev DD Electrical Installation May 2016 Electrical Installation ...
Страница 162: ...148 Reference Manual 00809 0100 4530 Rev DD Operation May 2016 Operation ...
Страница 214: ...200 Reference Manual 00809 0100 4530 Rev DD Service and Troubleshooting May 2016 Service and Troubleshooting ...
Страница 310: ...Product Certifications May 2016 Reference Manual 00809 0100 4530 Rev DD 296 Product Certifications ...
Страница 358: ...Level Transducer Block May 2016 Reference Manual 00809 0100 4530 Rev DD 344 Level Transducer Block ...
Страница 431: ...5 Reference Manual 00809 0100 4530 Rev DD May 2016 ...