109
Reference Manual
00809-0100-4530, Rev DD
May 2016
Tank environment
8.
Specify tank environment.
HART command: [2, 1, 4].
F
OUNDATION
Fieldbus parameter:
TRANSDUCER 1100 > MEAS_MODE
TRANSDUCER 1100 > PRODUCT_DIELEC_RANGE
TRANSDUCER 1100 > UPPER_PRODUCT_DC
Measurement mode
Normally, the measurement mode does not need to be changed. The transmitter is
pre-configured according to the specified model. See
“Basic configuration parameters” on
for more information.
Product dielectric range/upper product dielectric constant
The dielectric constant of the product is used for setting the appropriate signal amplitude
thresholds, see
Section 7: Service and Troubleshooting
for more information on amplitude
threshold settings.
For
interface level
measurements, the dielectric constant of the upper product is essential
for calculating interface level and the upper product thickness. By default, the
Upper
Product Dielectric Constant
parameter is about 2.
Set the
Upper Product Dielectric Constant
to a value that corresponds to the current
product.
Содержание 5300 Series
Страница 2: ......
Страница 12: ...Reference Manual 00809 0100 4530 Rev DD Contents May 2016 xii Contents ...
Страница 94: ...80 Reference Manual 00809 0100 4530 Rev DD Electrical Installation May 2016 Electrical Installation ...
Страница 162: ...148 Reference Manual 00809 0100 4530 Rev DD Operation May 2016 Operation ...
Страница 214: ...200 Reference Manual 00809 0100 4530 Rev DD Service and Troubleshooting May 2016 Service and Troubleshooting ...
Страница 310: ...Product Certifications May 2016 Reference Manual 00809 0100 4530 Rev DD 296 Product Certifications ...
Страница 358: ...Level Transducer Block May 2016 Reference Manual 00809 0100 4530 Rev DD 344 Level Transducer Block ...
Страница 431: ...5 Reference Manual 00809 0100 4530 Rev DD May 2016 ...