4.7.4
Intrinsically safe output
For intrinsically safe installations wire the transmitter as shown in
.
Note
Make sure the instruments in the loop are installed in accordance with intrinsically safe field
wiring practices and system control drawings when applicable.
Figure 4-6. Wiring Diagram for Intrinsically Safe Installations (HART)
For HART communication, a minimum load resistance of 250
within the loop is required.
For maximum load resistance see
.
The power supply voltage ranges from 16 Vdc to 30 Vdc.
IS parameters
(1)
U
i
= 30 V
I
i
= 130 mA
P
i
= 1 W
C
i
= 7.26 nF
L
i
= 0
1. See
Appendix B: Product Certifications
for more information.
Load resistance
Power
supply
Field
Communicator
Rosemount 5300 Series
Radar Transmitter
HART modem
RRM
AMS Suite
250
Approved IS barrier
Содержание 5300 Series
Страница 2: ......
Страница 12: ...Reference Manual 00809 0100 4530 Rev DD Contents May 2016 xii Contents ...
Страница 94: ...80 Reference Manual 00809 0100 4530 Rev DD Electrical Installation May 2016 Electrical Installation ...
Страница 162: ...148 Reference Manual 00809 0100 4530 Rev DD Operation May 2016 Operation ...
Страница 214: ...200 Reference Manual 00809 0100 4530 Rev DD Service and Troubleshooting May 2016 Service and Troubleshooting ...
Страница 310: ...Product Certifications May 2016 Reference Manual 00809 0100 4530 Rev DD 296 Product Certifications ...
Страница 358: ...Level Transducer Block May 2016 Reference Manual 00809 0100 4530 Rev DD 344 Level Transducer Block ...
Страница 431: ...5 Reference Manual 00809 0100 4530 Rev DD May 2016 ...