Appendix Function Parameter List
152
automatically by “P132: Motor Constant Measuring Function”.
・
Overcurrent trip may occur if the value of voltage compensation constant is
too large.
・
The torque may be insufficient at lower speed if the value of voltage
compensation contant is too small.
・
The change from manual torqe boost to auto torque boost or vice versa
cannot be made during operation.
●
Please use the inverter in the following conditions when set to “auto torque
boost”.
・
The motor must be the squirrel-cage induction type for general purpose.
・
Please select the inverter with capacity equivalent to or one level higher
than motor capacity.
Example 1) Please select a 0.75 kW inverter for motor ranging from 0.4 kW to
0.75 kW.
Example 2) Please select a 1.5 kW inverter for motor ranging from 0.75 kW to
1.5 kW.
・
Number of motor poles must be “2”, “4” or “6”.
・
It must operate in standalone mode (i.e., one motor is driven by one
inverter).
・
The maximum wiring length between the inverter and motor must not exceed
30 m.
If the above conditions are not satisfied, it is unlikely to achieve sound
operation performance.
・
The output frequency for auto torque boost setting ranges from 1 Hz to 120
Hz.
Содержание VF200
Страница 1: ...VF200 WME VF200 A 2013 01 panasonic net id pidsx global ...
Страница 2: ......
Страница 7: ......
Страница 8: ...1 Safety Precautions ...
Страница 14: ...Safety Precautions 7 7 Warning Label on Inverter VF200 ...
Страница 15: ...Safety Precautions 8 ...
Страница 16: ...9 Points for Handling Special Precautions 10 ...
Страница 19: ...Points for Handling ...
Страница 20: ...13 1 Parts Identification 1 1 Part Names and Functions 14 1 2 Details on Part Number 16 ...
Страница 29: ...2 Installation 22 VF200 ...
Страница 49: ...42 ...
Страница 56: ...4 Operation Method Basic Operation ...
Страница 66: ...4 Operation Method Basic Operation 7 Stop operation Press button The motor starts to decelerate till to stop ...
Страница 75: ...4 Operation Method Basic Operation ...
Страница 76: ...69 5 Control Status Monitor 5 1 List of Control Status Monitor Items 70 5 2 Introduction of Monitor No 72 ...
Страница 88: ...81 6 Function Parameters 6 1 Setting and Changing Function Parameters 8 6 2 Function Parameter List 83 ...
Страница 101: ...6 Function Parameters 94 ...
Страница 102: ...95 7 Custom Mode 7 1 Allocating Parameter No 96 7 2 Setting and Changing Parameters 98 ...
Страница 107: ...7 Custom Mode 100 ...
Страница 119: ...8 Setting Mode and Copy Function of Built in Memory 112 ...
Страница 126: ...9 Troubleshooting 119 9 3 3 Breaker Trip 9 3 4 Motor Overheating 9 3 5 Communication Failed ...
Страница 127: ...9 Troubleshooting 120 ...
Страница 136: ...129 11 Specifications 11 1 Rated Specifications 130 11 2 Standard Specifications 132 11 3 Common Specifications 133 ...
Страница 145: ...11 Specifications 138 ...
Страница 146: ...139 Appendix Function Parameter List ...
Страница 208: ...Appendix Function Parameter List 201 ...