Appendix Function Parameter List
221
・
When frequency setting signal is set with digitial or communication method,
the inverter will not perform 0 V stop.
・
If frequency setting signal is lower than 1/100 (1%) of full scale, the
command value will become 0 Hz.
Related parameters: P004, P099, P125
P102
P103
P104
Bias/Gain Function Select
Bias Frequency Setting
Gain Frequency Setting
The relationship between output frequency and frequency setting signal
(frequency setting analog signal of control circuit terminal No.14 or
potentiometer) can be adjusted freely. Please use this function according to
the applications.
■
Parameter P102: Bias/Gain Function Select
Setting
value
Details
0
Without bias/gain function
1
With bias/gain function
■
Parameter P103: Bias Frequency Setting
Data setting range (%)
-
99.0 to 250.0
■
Parameter P104: Gain Frequency Setting
Data setting range (%) 0.0 to 500.0
・
Bias frequency and gain frequency are set with the ratio (%) of 100%
maximum output frequency (parameter P008).
・
The frequency exceeding the maximum frequency or the upper frequency
limit will not be output.
Also, the frequency will not drop below the lower frequency limit.
・
The inverter will not perform reverse run operation even if negative
frequency setting signal is input.
Содержание VF200
Страница 1: ...VF200 WME VF200 A 2013 01 panasonic net id pidsx global ...
Страница 2: ......
Страница 7: ......
Страница 8: ...1 Safety Precautions ...
Страница 14: ...Safety Precautions 7 7 Warning Label on Inverter VF200 ...
Страница 15: ...Safety Precautions 8 ...
Страница 16: ...9 Points for Handling Special Precautions 10 ...
Страница 19: ...Points for Handling ...
Страница 20: ...13 1 Parts Identification 1 1 Part Names and Functions 14 1 2 Details on Part Number 16 ...
Страница 29: ...2 Installation 22 VF200 ...
Страница 49: ...42 ...
Страница 56: ...4 Operation Method Basic Operation ...
Страница 66: ...4 Operation Method Basic Operation 7 Stop operation Press button The motor starts to decelerate till to stop ...
Страница 75: ...4 Operation Method Basic Operation ...
Страница 76: ...69 5 Control Status Monitor 5 1 List of Control Status Monitor Items 70 5 2 Introduction of Monitor No 72 ...
Страница 88: ...81 6 Function Parameters 6 1 Setting and Changing Function Parameters 8 6 2 Function Parameter List 83 ...
Страница 101: ...6 Function Parameters 94 ...
Страница 102: ...95 7 Custom Mode 7 1 Allocating Parameter No 96 7 2 Setting and Changing Parameters 98 ...
Страница 107: ...7 Custom Mode 100 ...
Страница 119: ...8 Setting Mode and Copy Function of Built in Memory 112 ...
Страница 126: ...9 Troubleshooting 119 9 3 3 Breaker Trip 9 3 4 Motor Overheating 9 3 5 Communication Failed ...
Страница 127: ...9 Troubleshooting 120 ...
Страница 136: ...129 11 Specifications 11 1 Rated Specifications 130 11 2 Standard Specifications 132 11 3 Common Specifications 133 ...
Страница 145: ...11 Specifications 138 ...
Страница 146: ...139 Appendix Function Parameter List ...
Страница 208: ...Appendix Function Parameter List 201 ...