Appendix Function Parameter List
1
89
P041
Input Logic Setting
Input signals can be detected by selecting “A contact input” or “B contact
input”.
■
Setting value
・
Contact A input = “0” : When SW (button) signal is OFF (terminal level is “L”),
ON will be detected.
·
Contact B input = “1”: When SW (switch) signal is ON (terminal level is “H”),
ON will be detected.
■
Setting method
・
Convert bit 0 to 4 to DEC format for input.
・
Input the sum of setting value
×
addition value into the setting data.
< Operation Example > When SW1 and SW2 are “B contact input” and the
other signals are “A contact input”
Setting value = (0
×
16) + (0
×
8 ) + (0
×
4) + (1
×
2) + (1
×
1) = 3
Terminal
name
Without
setting
SW5
SW4
SW3
SW2
SW1
Terminal
No.
-
⑧
⑦
⑥
⑤
④
Bit
5 to 15
4
3
2
1
0
Setting
value
0
/
1 0
/
1 0
/
1 0
/
1 0
/
1 0
/
1
Addition
value
- 16 8 4 2 1
・
Due to the fact that ON/OFF status of each SW will change with the input
logic setting, so check the input logic setting before using.
・
Forward/reverse run and run/stop are fixed to “contact A input”.
・
When each SW function is set to “3-wire stop command function”, “contact
B input” always applies even if “Input Logic Setting” is set to “contact A input”.
Related parameters: P036 to P040
Содержание VF200
Страница 1: ...VF200 WME VF200 A 2013 01 panasonic net id pidsx global ...
Страница 2: ......
Страница 7: ......
Страница 8: ...1 Safety Precautions ...
Страница 14: ...Safety Precautions 7 7 Warning Label on Inverter VF200 ...
Страница 15: ...Safety Precautions 8 ...
Страница 16: ...9 Points for Handling Special Precautions 10 ...
Страница 19: ...Points for Handling ...
Страница 20: ...13 1 Parts Identification 1 1 Part Names and Functions 14 1 2 Details on Part Number 16 ...
Страница 29: ...2 Installation 22 VF200 ...
Страница 49: ...42 ...
Страница 56: ...4 Operation Method Basic Operation ...
Страница 66: ...4 Operation Method Basic Operation 7 Stop operation Press button The motor starts to decelerate till to stop ...
Страница 75: ...4 Operation Method Basic Operation ...
Страница 76: ...69 5 Control Status Monitor 5 1 List of Control Status Monitor Items 70 5 2 Introduction of Monitor No 72 ...
Страница 88: ...81 6 Function Parameters 6 1 Setting and Changing Function Parameters 8 6 2 Function Parameter List 83 ...
Страница 101: ...6 Function Parameters 94 ...
Страница 102: ...95 7 Custom Mode 7 1 Allocating Parameter No 96 7 2 Setting and Changing Parameters 98 ...
Страница 107: ...7 Custom Mode 100 ...
Страница 119: ...8 Setting Mode and Copy Function of Built in Memory 112 ...
Страница 126: ...9 Troubleshooting 119 9 3 3 Breaker Trip 9 3 4 Motor Overheating 9 3 5 Communication Failed ...
Страница 127: ...9 Troubleshooting 120 ...
Страница 136: ...129 11 Specifications 11 1 Rated Specifications 130 11 2 Standard Specifications 132 11 3 Common Specifications 133 ...
Страница 145: ...11 Specifications 138 ...
Страница 146: ...139 Appendix Function Parameter List ...
Страница 208: ...Appendix Function Parameter List 201 ...