3. Wiring
39
■
Wiring for PWM/Pulse input controlled Operating Frequency Mode (Terminal No.7, 8)
·
When parameter P087 is set to "1”, the operating frequency will be controlled
by external PWM signal from PLC, etc.
·
When parameter P087 is set to "2”, the operating frequency will be controlled
by external pulse signal from PLC, etc.
·
Terminal No.7 is the input terminal for changeover of frequency setting signal
(SW4) (OFF: PWM/Pulse input signal, ON: controlled by the signal set in parameter P004),
while terminal No.8 is the input terminal for PWM/Pulse input signal .
·
As for the transistor for PWM/Pulse input signal, please use one with maximum
voltage rating over 50 V and maximum current rating over 50 mA.
·
In addition, to use PWM signal for operating frequency control, relevant
settings must be made to parameter P088 and P089.
·
Use pulse signal for operating frequency control, relevant settings must be
made to parameter P174.
·
When setting value is "1" or "2", the SW function for SW4(terminal No.7) and
SW5(terminal No.8) will be forced to be used for controlling PWM/pulse signal only.
■
Wiring for Open-collector Output Terminals (Terminal No.10 to 12)
·
When using open-collector output terminals to drive inductive loads, always
connect a freewheel diode.
⑦
⑧
⑨
PWM Signal
⑦
⑧
⑨
Pulse input signal
Содержание VF200
Страница 1: ...VF200 WME VF200 A 2013 01 panasonic net id pidsx global ...
Страница 2: ......
Страница 7: ......
Страница 8: ...1 Safety Precautions ...
Страница 14: ...Safety Precautions 7 7 Warning Label on Inverter VF200 ...
Страница 15: ...Safety Precautions 8 ...
Страница 16: ...9 Points for Handling Special Precautions 10 ...
Страница 19: ...Points for Handling ...
Страница 20: ...13 1 Parts Identification 1 1 Part Names and Functions 14 1 2 Details on Part Number 16 ...
Страница 29: ...2 Installation 22 VF200 ...
Страница 49: ...42 ...
Страница 56: ...4 Operation Method Basic Operation ...
Страница 66: ...4 Operation Method Basic Operation 7 Stop operation Press button The motor starts to decelerate till to stop ...
Страница 75: ...4 Operation Method Basic Operation ...
Страница 76: ...69 5 Control Status Monitor 5 1 List of Control Status Monitor Items 70 5 2 Introduction of Monitor No 72 ...
Страница 88: ...81 6 Function Parameters 6 1 Setting and Changing Function Parameters 8 6 2 Function Parameter List 83 ...
Страница 101: ...6 Function Parameters 94 ...
Страница 102: ...95 7 Custom Mode 7 1 Allocating Parameter No 96 7 2 Setting and Changing Parameters 98 ...
Страница 107: ...7 Custom Mode 100 ...
Страница 119: ...8 Setting Mode and Copy Function of Built in Memory 112 ...
Страница 126: ...9 Troubleshooting 119 9 3 3 Breaker Trip 9 3 4 Motor Overheating 9 3 5 Communication Failed ...
Страница 127: ...9 Troubleshooting 120 ...
Страница 136: ...129 11 Specifications 11 1 Rated Specifications 130 11 2 Standard Specifications 132 11 3 Common Specifications 133 ...
Страница 145: ...11 Specifications 138 ...
Страница 146: ...139 Appendix Function Parameter List ...
Страница 208: ...Appendix Function Parameter List 201 ...