11. Specifications
13
1
Note 1) Rated output current of 3.7 kW+ inverters varies with the set carrier
frequency. Derate the output current as shown in the following figure.
•
3.7 kW to 11 kW Type
•
15 kW Type
Note 2) Rated output capacity: refers to the value at output voltage of 230 VAC
for 1-phase 200 V type and the value at output voltage of 460 VAC for
3-phase 400 V type.
Note 3) The power supply capacity varies with source impedance. Please use
a power supply as shown on the above table.
Note 4) If excessive amount of current flows through the circuit repeatedly or
the unit is used under high temperature, overcurrent trip may occur.
•
For 200 V/0.75 kW inverter, if the carrier frequency is above 7.5 kHz,
overcurrent trip will occur to cause reduction of overcurrent protection
capability.
•
For 200 V/1.5 kW inverter, if the carrier frequency is above 5 kHz, overcurrent
trip will occur to cause reduction of overcurrent protection capability.
Содержание VF200
Страница 1: ...VF200 WME VF200 A 2013 01 panasonic net id pidsx global ...
Страница 2: ......
Страница 7: ......
Страница 8: ...1 Safety Precautions ...
Страница 14: ...Safety Precautions 7 7 Warning Label on Inverter VF200 ...
Страница 15: ...Safety Precautions 8 ...
Страница 16: ...9 Points for Handling Special Precautions 10 ...
Страница 19: ...Points for Handling ...
Страница 20: ...13 1 Parts Identification 1 1 Part Names and Functions 14 1 2 Details on Part Number 16 ...
Страница 29: ...2 Installation 22 VF200 ...
Страница 49: ...42 ...
Страница 56: ...4 Operation Method Basic Operation ...
Страница 66: ...4 Operation Method Basic Operation 7 Stop operation Press button The motor starts to decelerate till to stop ...
Страница 75: ...4 Operation Method Basic Operation ...
Страница 76: ...69 5 Control Status Monitor 5 1 List of Control Status Monitor Items 70 5 2 Introduction of Monitor No 72 ...
Страница 88: ...81 6 Function Parameters 6 1 Setting and Changing Function Parameters 8 6 2 Function Parameter List 83 ...
Страница 101: ...6 Function Parameters 94 ...
Страница 102: ...95 7 Custom Mode 7 1 Allocating Parameter No 96 7 2 Setting and Changing Parameters 98 ...
Страница 107: ...7 Custom Mode 100 ...
Страница 119: ...8 Setting Mode and Copy Function of Built in Memory 112 ...
Страница 126: ...9 Troubleshooting 119 9 3 3 Breaker Trip 9 3 4 Motor Overheating 9 3 5 Communication Failed ...
Страница 127: ...9 Troubleshooting 120 ...
Страница 136: ...129 11 Specifications 11 1 Rated Specifications 130 11 2 Standard Specifications 132 11 3 Common Specifications 133 ...
Страница 145: ...11 Specifications 138 ...
Страница 146: ...139 Appendix Function Parameter List ...
Страница 208: ...Appendix Function Parameter List 201 ...