Appendix Function Parameter List
22
6
■
Parameter P109: Derivative Time [Td]
Data setting range (s) 0000
·
0.1 to 3600
* “0000” indicates that there is no derivative control.
■
Parameter P110: Control Cycle [Ts]
Data setting range (s) 0.01 to 60.00
■
Parameter P111: PID Target Value
Data setting range (%) 0.0
·
0.1 to 100.0
Related parameters: P004, P036 to P040, P099, P102 to P104, P124 to P127
■
Setting procedures of PID control
1. PID control select
・
“P124: The 2
nd
Analog Input Function Select” is set to “1” or “2”.
“1” and “2” will be treated as “measured value” and “bias signal”
respectively.
・
When parameter P142 = “0” or “3”, PID control will not be performed.
2. Measured value (PV)
・
“P125: The 2
nd
Analog Input Signal Select”
is set to the signal specification of the
detector.
・
The relationship between detector signal
and measured value (PV) is set with “P126:
The 2
nd
Bias Frequency Setting” and “P127:
The 2
nd
Gain Frequency”.
<Example> 4 mA = 0
%
, 20 mA = 100
%
・
Bias can be added with “P157: The 2
nd
Analog Superimposed Value”.
Содержание VF200
Страница 1: ...VF200 WME VF200 A 2013 01 panasonic net id pidsx global ...
Страница 2: ......
Страница 7: ......
Страница 8: ...1 Safety Precautions ...
Страница 14: ...Safety Precautions 7 7 Warning Label on Inverter VF200 ...
Страница 15: ...Safety Precautions 8 ...
Страница 16: ...9 Points for Handling Special Precautions 10 ...
Страница 19: ...Points for Handling ...
Страница 20: ...13 1 Parts Identification 1 1 Part Names and Functions 14 1 2 Details on Part Number 16 ...
Страница 29: ...2 Installation 22 VF200 ...
Страница 49: ...42 ...
Страница 56: ...4 Operation Method Basic Operation ...
Страница 66: ...4 Operation Method Basic Operation 7 Stop operation Press button The motor starts to decelerate till to stop ...
Страница 75: ...4 Operation Method Basic Operation ...
Страница 76: ...69 5 Control Status Monitor 5 1 List of Control Status Monitor Items 70 5 2 Introduction of Monitor No 72 ...
Страница 88: ...81 6 Function Parameters 6 1 Setting and Changing Function Parameters 8 6 2 Function Parameter List 83 ...
Страница 101: ...6 Function Parameters 94 ...
Страница 102: ...95 7 Custom Mode 7 1 Allocating Parameter No 96 7 2 Setting and Changing Parameters 98 ...
Страница 107: ...7 Custom Mode 100 ...
Страница 119: ...8 Setting Mode and Copy Function of Built in Memory 112 ...
Страница 126: ...9 Troubleshooting 119 9 3 3 Breaker Trip 9 3 4 Motor Overheating 9 3 5 Communication Failed ...
Страница 127: ...9 Troubleshooting 120 ...
Страница 136: ...129 11 Specifications 11 1 Rated Specifications 130 11 2 Standard Specifications 132 11 3 Common Specifications 133 ...
Страница 145: ...11 Specifications 138 ...
Страница 146: ...139 Appendix Function Parameter List ...
Страница 208: ...Appendix Function Parameter List 201 ...