9. Troubleshooting
114
9.1 Safety Precautions
Wait at least five minutes after turning off the input
power before starting maintenance and inspection work.
Failure to do so may result in an electric shock.
Maintenance, inspection and part replacement work
must be done only by qualified persons.
(Remove metal articles such as watch, bracelet(s) etc.
before operation.)
(Please use insulated tools.)
Failure to do so may result in an electric shock or injury.
9.2 Abnormality Diagnostic Function and
Resetting Method
9.2.1 Details and Remedies for Various Fault Trips
The fault trip memory stores the causes of trip in monitor modes n20 to n23.
Even if the power is cut off, the fourth to the latest causes of trip will still be held.
(Details of factory inspection are stored in the memory before delivery.)
Indication
Details and causes of abnormality
Remedies
SC1
•
Instantaneous overcurrent during
acceleration or cooling fan malfunction
SC2
•
Instantaneous overcurrent at constant
speed or cooling fan malfunction
SC3
•
Instantaneous overcurrent during
deceleration or cooling fan malfunction
SC4
•
Instantaneous overcurrent during
deceleration
SC5
•
Instantaneous overcurrent at constant
speed
SC6
•
Instantaneous overcurrent during
acceleration
•
Check if there is any shorted output
or ground.
•
Remove sharp variations at load
side.
•
Extend acceleration/deceleration
time (parameters P001, P002 and
P061 to P066).
•
Check the operation of cooling fan.
•
Stop open and close operation of
magnetic contactor at load side.
Содержание VF200
Страница 1: ...VF200 WME VF200 A 2013 01 panasonic net id pidsx global ...
Страница 2: ......
Страница 7: ......
Страница 8: ...1 Safety Precautions ...
Страница 14: ...Safety Precautions 7 7 Warning Label on Inverter VF200 ...
Страница 15: ...Safety Precautions 8 ...
Страница 16: ...9 Points for Handling Special Precautions 10 ...
Страница 19: ...Points for Handling ...
Страница 20: ...13 1 Parts Identification 1 1 Part Names and Functions 14 1 2 Details on Part Number 16 ...
Страница 29: ...2 Installation 22 VF200 ...
Страница 49: ...42 ...
Страница 56: ...4 Operation Method Basic Operation ...
Страница 66: ...4 Operation Method Basic Operation 7 Stop operation Press button The motor starts to decelerate till to stop ...
Страница 75: ...4 Operation Method Basic Operation ...
Страница 76: ...69 5 Control Status Monitor 5 1 List of Control Status Monitor Items 70 5 2 Introduction of Monitor No 72 ...
Страница 88: ...81 6 Function Parameters 6 1 Setting and Changing Function Parameters 8 6 2 Function Parameter List 83 ...
Страница 101: ...6 Function Parameters 94 ...
Страница 102: ...95 7 Custom Mode 7 1 Allocating Parameter No 96 7 2 Setting and Changing Parameters 98 ...
Страница 107: ...7 Custom Mode 100 ...
Страница 119: ...8 Setting Mode and Copy Function of Built in Memory 112 ...
Страница 126: ...9 Troubleshooting 119 9 3 3 Breaker Trip 9 3 4 Motor Overheating 9 3 5 Communication Failed ...
Страница 127: ...9 Troubleshooting 120 ...
Страница 136: ...129 11 Specifications 11 1 Rated Specifications 130 11 2 Standard Specifications 132 11 3 Common Specifications 133 ...
Страница 145: ...11 Specifications 138 ...
Страница 146: ...139 Appendix Function Parameter List ...
Страница 208: ...Appendix Function Parameter List 201 ...