Appendix Function Parameter List
212
P090
P091
Output TR1 Function Select
Output TR2 Function Select
Functions of open-collector output 1 (control circuit terminal No.10 to No.12)
and open-collector output 2 (control circuit terminal No.11 to No.12) can be
set.
TR1P090 TR2P091
Function
ON conditions for open-collector
output
0 0
Run signal
With run signal ON or during inverter
output
1 1
Reverse run
signal
When inverter is in reverse run status
2 2
Arrival signal
When output frequency is within
±
2
Hz of setting frequency
3 3
Overload alarm
When the output current is above
140% of the rated current or the
electronic thermal level is reached.
4 4
Frequency
sensing
When the output frequency is above
sensing frequency (parameter P093
setting).
5 5
Current sensing
(1)
When the output current is above the
sensing current level (parameter
P095 setting).
6 6
Current sensing
(2)
When the output current is below the
sensing current level (parameter
P095 setting).
7 7
Fault alarm (1)
When fault trip occurs in the inverter
8 8
Fault alarm (2)
When the inverter is in normal status
(OFF for fault trip status)
9 9
After one cycle of
timer operation
When one cycle of timer operation
completes (output is available only
during waiting time)
10 10
Timer operation
completed
When timer operation completes
(with “tEnd” displayed)
Setting
value
11 11
Alarm
Output is available with alarm LED
flickering.
Содержание VF200
Страница 1: ...VF200 WME VF200 A 2013 01 panasonic net id pidsx global ...
Страница 2: ......
Страница 7: ......
Страница 8: ...1 Safety Precautions ...
Страница 14: ...Safety Precautions 7 7 Warning Label on Inverter VF200 ...
Страница 15: ...Safety Precautions 8 ...
Страница 16: ...9 Points for Handling Special Precautions 10 ...
Страница 19: ...Points for Handling ...
Страница 20: ...13 1 Parts Identification 1 1 Part Names and Functions 14 1 2 Details on Part Number 16 ...
Страница 29: ...2 Installation 22 VF200 ...
Страница 49: ...42 ...
Страница 56: ...4 Operation Method Basic Operation ...
Страница 66: ...4 Operation Method Basic Operation 7 Stop operation Press button The motor starts to decelerate till to stop ...
Страница 75: ...4 Operation Method Basic Operation ...
Страница 76: ...69 5 Control Status Monitor 5 1 List of Control Status Monitor Items 70 5 2 Introduction of Monitor No 72 ...
Страница 88: ...81 6 Function Parameters 6 1 Setting and Changing Function Parameters 8 6 2 Function Parameter List 83 ...
Страница 101: ...6 Function Parameters 94 ...
Страница 102: ...95 7 Custom Mode 7 1 Allocating Parameter No 96 7 2 Setting and Changing Parameters 98 ...
Страница 107: ...7 Custom Mode 100 ...
Страница 119: ...8 Setting Mode and Copy Function of Built in Memory 112 ...
Страница 126: ...9 Troubleshooting 119 9 3 3 Breaker Trip 9 3 4 Motor Overheating 9 3 5 Communication Failed ...
Страница 127: ...9 Troubleshooting 120 ...
Страница 136: ...129 11 Specifications 11 1 Rated Specifications 130 11 2 Standard Specifications 132 11 3 Common Specifications 133 ...
Страница 145: ...11 Specifications 138 ...
Страница 146: ...139 Appendix Function Parameter List ...
Страница 208: ...Appendix Function Parameter List 201 ...