Appendix Function Parameter List
250
■
Operation procedure of automatic tuning
1. Switch to automatic tuning mode setting
・
When voltage compensation constant is measured, P132 is set to “1”.
・
When slip compensation frequency is measured: P132 is set to “2”.
2. Enter measurement ready status
Press
button to enter operation status display mode.
・
Displayed when voltage compensation constant is
measured (P132 = “1”)
・
Displayed when slip compensation frequency is
measured (P132 = “2”)
3. Automatic tuning starts
Press
button to start automatic tuning.
・
When voltage compensation constant is measured
Normally the inverter will automatically apply high DC
voltage to the motor for 2 s. The display flickers during
measurement (P132 = “1”).
・
When slip compensation frequency is measured
The inverter will drive the motor automatically at 60 Hz.
The tuning operation will normally last until (the 1
st
acceleration time + 5 s) has elapsed. The display flickers
during measurement (P132 = “2”).
4. Automatic tuning completes
When automatic tuning completes, data will be written to
parameter P133 or P134 automatically, indicating that
automatic tuning is complete.
・
The display indicate that voltage compensation constant
measurement is complete.
・
The display indicate that frequency compensation
frequency measurement is complete.
Содержание VF200
Страница 1: ...VF200 WME VF200 A 2013 01 panasonic net id pidsx global ...
Страница 2: ......
Страница 7: ......
Страница 8: ...1 Safety Precautions ...
Страница 14: ...Safety Precautions 7 7 Warning Label on Inverter VF200 ...
Страница 15: ...Safety Precautions 8 ...
Страница 16: ...9 Points for Handling Special Precautions 10 ...
Страница 19: ...Points for Handling ...
Страница 20: ...13 1 Parts Identification 1 1 Part Names and Functions 14 1 2 Details on Part Number 16 ...
Страница 29: ...2 Installation 22 VF200 ...
Страница 49: ...42 ...
Страница 56: ...4 Operation Method Basic Operation ...
Страница 66: ...4 Operation Method Basic Operation 7 Stop operation Press button The motor starts to decelerate till to stop ...
Страница 75: ...4 Operation Method Basic Operation ...
Страница 76: ...69 5 Control Status Monitor 5 1 List of Control Status Monitor Items 70 5 2 Introduction of Monitor No 72 ...
Страница 88: ...81 6 Function Parameters 6 1 Setting and Changing Function Parameters 8 6 2 Function Parameter List 83 ...
Страница 101: ...6 Function Parameters 94 ...
Страница 102: ...95 7 Custom Mode 7 1 Allocating Parameter No 96 7 2 Setting and Changing Parameters 98 ...
Страница 107: ...7 Custom Mode 100 ...
Страница 119: ...8 Setting Mode and Copy Function of Built in Memory 112 ...
Страница 126: ...9 Troubleshooting 119 9 3 3 Breaker Trip 9 3 4 Motor Overheating 9 3 5 Communication Failed ...
Страница 127: ...9 Troubleshooting 120 ...
Страница 136: ...129 11 Specifications 11 1 Rated Specifications 130 11 2 Standard Specifications 132 11 3 Common Specifications 133 ...
Страница 145: ...11 Specifications 138 ...
Страница 146: ...139 Appendix Function Parameter List ...
Страница 208: ...Appendix Function Parameter List 201 ...