3. Wiring
3.3.2 Precautions on Wiring Main Circuit
■
Precautions on Wiring
To avoid mistakes in wiring and operation, be sure to observe the following
guides.(Failure to do so may damage the unit.)
·
Always connect the power source to input terminals (R/L1, S/L2, T/L3), and
connect the motor to output terminals (U,V,W).
·
Use round crimp terminals with sleeve for power source and motor
connections. Select crimp terminals according to wire sizes and screw sizes.
·
After wiring main circuit, confirm the tightening condition of terminals.
·
Main circuit must be wired prior to control circuit. Otherwise, re-tightening
operation is not possible after control circuit wiring is completed.
·
When connecting directly to a transformer of large capacity (500 kVA or more),
always install an AC reactor on the input side of the inverter.
Note 1:
It is recommended to use teflon insulated wire (600 V, Class 2,
allowable operating temperature up to 75 °C) for main circuit wiring.
Note 2:
Use wires with larger diameter if the wiring distance is long.
Note 3:
If the overcurrent trip of the circuit breaker is magnetic type, the
device could become overheated due to higher harmonics. Use a
load rate of 50% or lower in this case.
Note 4:
If a circuit breaker for motor protection is in use, remove it.
Note 5:
Always connect protective devices against overcurrent, short-circuit
and current leakage on the input side.
■
Precautions on Using Regenerative Brakes
·
When using regenerative brakes, set the parameter P019 to "0". Since the
factory setting is "1", the brakes will not be activated.
·
Specifications for regenerative brakes are shown as follows. Carefully
consider the operation conditions before using them. Note that the inverter
could be damaged if a brake outside specifications is used.
Max. duty factor (%ED): 5%
·
Max. operating time: 5 s
·
Max. torque: 100%
Содержание VF200
Страница 1: ...VF200 WME VF200 A 2013 01 panasonic net id pidsx global ...
Страница 2: ......
Страница 7: ......
Страница 8: ...1 Safety Precautions ...
Страница 14: ...Safety Precautions 7 7 Warning Label on Inverter VF200 ...
Страница 15: ...Safety Precautions 8 ...
Страница 16: ...9 Points for Handling Special Precautions 10 ...
Страница 19: ...Points for Handling ...
Страница 20: ...13 1 Parts Identification 1 1 Part Names and Functions 14 1 2 Details on Part Number 16 ...
Страница 29: ...2 Installation 22 VF200 ...
Страница 49: ...42 ...
Страница 56: ...4 Operation Method Basic Operation ...
Страница 66: ...4 Operation Method Basic Operation 7 Stop operation Press button The motor starts to decelerate till to stop ...
Страница 75: ...4 Operation Method Basic Operation ...
Страница 76: ...69 5 Control Status Monitor 5 1 List of Control Status Monitor Items 70 5 2 Introduction of Monitor No 72 ...
Страница 88: ...81 6 Function Parameters 6 1 Setting and Changing Function Parameters 8 6 2 Function Parameter List 83 ...
Страница 101: ...6 Function Parameters 94 ...
Страница 102: ...95 7 Custom Mode 7 1 Allocating Parameter No 96 7 2 Setting and Changing Parameters 98 ...
Страница 107: ...7 Custom Mode 100 ...
Страница 119: ...8 Setting Mode and Copy Function of Built in Memory 112 ...
Страница 126: ...9 Troubleshooting 119 9 3 3 Breaker Trip 9 3 4 Motor Overheating 9 3 5 Communication Failed ...
Страница 127: ...9 Troubleshooting 120 ...
Страница 136: ...129 11 Specifications 11 1 Rated Specifications 130 11 2 Standard Specifications 132 11 3 Common Specifications 133 ...
Страница 145: ...11 Specifications 138 ...
Страница 146: ...139 Appendix Function Parameter List ...
Страница 208: ...Appendix Function Parameter List 201 ...