4. Operation Method (Basic Operation)
4.5 Setting Frequency with Operation Panel
There are 2 modes to set frequency with operation panel as follows.
■
Potentiometer Setting Mode (Parameter P004 is set to “0”: factory setting.)
Adjust the position of potentiometer dial on operation panel to make setting.
MIN. position stands for operation stop (0V stop: see parameter P101), while
MAX. position for the maximum frequency.
■
Digital Setting Mode (Parameter P004 is set to “1”.)
Press MODE button on the panel to enter frequency setting mode (display: Fr);
press SET button and display the frequency to be set by pressing UP and DOWN
buttons and then press SET button again to complete the setting. Also, the
following “MOP function” can be used for frequency setting during operation.
MOP function
The frequency can be changed by pressing and holding UP or DOWN button
during operation. However, if parameter P003 is set to “1”, this function does not
work.
The operation will vary according to the settings of “Parameters” P154: MOP
Function Select” and “P155: MOP Operation Acceleration/Deceleration Time”.
Содержание VF200
Страница 1: ...VF200 WME VF200 A 2013 01 panasonic net id pidsx global ...
Страница 2: ......
Страница 7: ......
Страница 8: ...1 Safety Precautions ...
Страница 14: ...Safety Precautions 7 7 Warning Label on Inverter VF200 ...
Страница 15: ...Safety Precautions 8 ...
Страница 16: ...9 Points for Handling Special Precautions 10 ...
Страница 19: ...Points for Handling ...
Страница 20: ...13 1 Parts Identification 1 1 Part Names and Functions 14 1 2 Details on Part Number 16 ...
Страница 29: ...2 Installation 22 VF200 ...
Страница 49: ...42 ...
Страница 56: ...4 Operation Method Basic Operation ...
Страница 66: ...4 Operation Method Basic Operation 7 Stop operation Press button The motor starts to decelerate till to stop ...
Страница 75: ...4 Operation Method Basic Operation ...
Страница 76: ...69 5 Control Status Monitor 5 1 List of Control Status Monitor Items 70 5 2 Introduction of Monitor No 72 ...
Страница 88: ...81 6 Function Parameters 6 1 Setting and Changing Function Parameters 8 6 2 Function Parameter List 83 ...
Страница 101: ...6 Function Parameters 94 ...
Страница 102: ...95 7 Custom Mode 7 1 Allocating Parameter No 96 7 2 Setting and Changing Parameters 98 ...
Страница 107: ...7 Custom Mode 100 ...
Страница 119: ...8 Setting Mode and Copy Function of Built in Memory 112 ...
Страница 126: ...9 Troubleshooting 119 9 3 3 Breaker Trip 9 3 4 Motor Overheating 9 3 5 Communication Failed ...
Страница 127: ...9 Troubleshooting 120 ...
Страница 136: ...129 11 Specifications 11 1 Rated Specifications 130 11 2 Standard Specifications 132 11 3 Common Specifications 133 ...
Страница 145: ...11 Specifications 138 ...
Страница 146: ...139 Appendix Function Parameter List ...
Страница 208: ...Appendix Function Parameter List 201 ...