Appendix Function Parameter List
17
7
■
External Fault Stop Function
Signal input terminal for applying fault stop (emergency stop) to the inverter
through external devices can be set.
・
The inverter will stop output immediately after the external fault stop input
(setting value = 4) turns SW signal ON and “AU” is displayed.
・
Input signal logic setting (contact A and B input select) can be set with “P041:
Input Logic Setting”.
< Example > When SW1 (parameter P036 = 4) is set to external fault stop,
and input logic setting (P041 = 1) and run command select (parameter P003 =
2) are used
* When external fault stop signal is set to contact B input, fault reset can be
applied after run signal is turn OFF, even if external stop signal is “ON”. But
fault trip will occur after the run signal is turned “ON” again. So please turn the
run signal “ON” after the external fault stop signal being turned “OFF” for
normal operation.
■
Parameter Setting Disable Function
The signal input terminal for disabling the parameter setting through external
control can be set.
・
After signal input is turned ON, setting parameters with the operation panel
and communication are disabled.
・
When the signal input is turned ON, function parameters and built-in memory
parameters cannot be set but be monitored.
・
During data setting, data cannot be changed even if SET button is pressed
when the signal is ON.
Содержание VF200
Страница 1: ...VF200 WME VF200 A 2013 01 panasonic net id pidsx global ...
Страница 2: ......
Страница 7: ......
Страница 8: ...1 Safety Precautions ...
Страница 14: ...Safety Precautions 7 7 Warning Label on Inverter VF200 ...
Страница 15: ...Safety Precautions 8 ...
Страница 16: ...9 Points for Handling Special Precautions 10 ...
Страница 19: ...Points for Handling ...
Страница 20: ...13 1 Parts Identification 1 1 Part Names and Functions 14 1 2 Details on Part Number 16 ...
Страница 29: ...2 Installation 22 VF200 ...
Страница 49: ...42 ...
Страница 56: ...4 Operation Method Basic Operation ...
Страница 66: ...4 Operation Method Basic Operation 7 Stop operation Press button The motor starts to decelerate till to stop ...
Страница 75: ...4 Operation Method Basic Operation ...
Страница 76: ...69 5 Control Status Monitor 5 1 List of Control Status Monitor Items 70 5 2 Introduction of Monitor No 72 ...
Страница 88: ...81 6 Function Parameters 6 1 Setting and Changing Function Parameters 8 6 2 Function Parameter List 83 ...
Страница 101: ...6 Function Parameters 94 ...
Страница 102: ...95 7 Custom Mode 7 1 Allocating Parameter No 96 7 2 Setting and Changing Parameters 98 ...
Страница 107: ...7 Custom Mode 100 ...
Страница 119: ...8 Setting Mode and Copy Function of Built in Memory 112 ...
Страница 126: ...9 Troubleshooting 119 9 3 3 Breaker Trip 9 3 4 Motor Overheating 9 3 5 Communication Failed ...
Страница 127: ...9 Troubleshooting 120 ...
Страница 136: ...129 11 Specifications 11 1 Rated Specifications 130 11 2 Standard Specifications 132 11 3 Common Specifications 133 ...
Страница 145: ...11 Specifications 138 ...
Страница 146: ...139 Appendix Function Parameter List ...
Страница 208: ...Appendix Function Parameter List 201 ...