Appendix Function Parameter List
14
4
P004
Frequency Setting Signal
The frequency setting signal can be selected with operation panel, signal
input from external devices or communication command.
Setting
value
Command
status
Details of signal
setting
Operation method and control circuit terminal
connection diagram
0
Potentiometer
setting
Potentiometer on the panel
MAX: maximum frequency (refer to P005 and
P008)
MIN: minimum frequency (or 0 V stop)
OP trip will occur if the operation panel is
removed during operation.
1
Panel
Digital setting
Can be set in “Frequency Setting Mode (Fr)”
2
Potentiometer
Terminal No.13, 14 and 15 (center of
potentiometer is connected to No.14)
3
0 to 5 V
(Voltage signal)
Terminal No.14 and 15 (14: +, 15: -)
4
0 to 10 V
(Voltage signal)
Terminal No. 14 and 15 (14: +, 15: -)
5
4 to 20 mA
(Current signal)
Terminal No.14 and 15 (14: +, 15: -): a 200
Ω
resistor is connected between 14 and 15.
6
External
Control
0 to 20 mA
(Current signal)
Terminal No.14 and 15 (14: +, 15: -): a 200
Ω
resistor is connected between 14 and 15.
7
Communication
RS485
communication
Make frequency command transmitted through
communication valid.
8
Panel
Potentiometer
setting
Potentiometer on the operation panel
MAX: maximum frequency (refer to P005 and
P008)
MIN: minimum frequency (or 0 V stop)
*Operation will continue even if the panel is
removed during operation.
・
If a 4 to 20 mA or 0 to 20 mA signal is used, please connect a “200
Ω
resistor” between terminal No.14 and 15.
(If the 200
Ω
resistor is not connected, the inverter could be damaged.)
・
When frequency setting signal is set to a value other than “1” or “7”, the
Содержание VF200
Страница 1: ...VF200 WME VF200 A 2013 01 panasonic net id pidsx global ...
Страница 2: ......
Страница 7: ......
Страница 8: ...1 Safety Precautions ...
Страница 14: ...Safety Precautions 7 7 Warning Label on Inverter VF200 ...
Страница 15: ...Safety Precautions 8 ...
Страница 16: ...9 Points for Handling Special Precautions 10 ...
Страница 19: ...Points for Handling ...
Страница 20: ...13 1 Parts Identification 1 1 Part Names and Functions 14 1 2 Details on Part Number 16 ...
Страница 29: ...2 Installation 22 VF200 ...
Страница 49: ...42 ...
Страница 56: ...4 Operation Method Basic Operation ...
Страница 66: ...4 Operation Method Basic Operation 7 Stop operation Press button The motor starts to decelerate till to stop ...
Страница 75: ...4 Operation Method Basic Operation ...
Страница 76: ...69 5 Control Status Monitor 5 1 List of Control Status Monitor Items 70 5 2 Introduction of Monitor No 72 ...
Страница 88: ...81 6 Function Parameters 6 1 Setting and Changing Function Parameters 8 6 2 Function Parameter List 83 ...
Страница 101: ...6 Function Parameters 94 ...
Страница 102: ...95 7 Custom Mode 7 1 Allocating Parameter No 96 7 2 Setting and Changing Parameters 98 ...
Страница 107: ...7 Custom Mode 100 ...
Страница 119: ...8 Setting Mode and Copy Function of Built in Memory 112 ...
Страница 126: ...9 Troubleshooting 119 9 3 3 Breaker Trip 9 3 4 Motor Overheating 9 3 5 Communication Failed ...
Страница 127: ...9 Troubleshooting 120 ...
Страница 136: ...129 11 Specifications 11 1 Rated Specifications 130 11 2 Standard Specifications 132 11 3 Common Specifications 133 ...
Страница 145: ...11 Specifications 138 ...
Страница 146: ...139 Appendix Function Parameter List ...
Страница 208: ...Appendix Function Parameter List 201 ...