Appendix Function Parameter List
21
4
P092
Output RY Function Select
Functions of relay output (control circuit terminal A, B and C) can be set.
・
Energizing in ON status: The relay is turned ON when the coil is energized.
(Signal ON status = ON between terminals A and
C, OFF between terminals B and C)
・
Non-energizing in ON status: the relay is turned ON when the coil is not
energized.
(Signal ON status = OFF between terminals A
and C, ON between terminals B and C)
Setting value
Energizing
in ON
status
Non-energizing
in ON status
Function
ON conditions for relay
0
r0 Run
signal
With run signal ON or during
inverter output
1
r1
Reverse run signal
When inverter is in reverse run
status
2
r2 Arrival
signal
When output frequency is within
±
2 Hz of setting frequency
3
r3 Overload
alarm
When the output current is above
140% of the rated current or the
electronic thermal level is
reached.
4
r4 Frequency
sensing
When the output frequency is
above sensing frequency
(parameter P094 setting).
5
r5
Current sensing (1)
When the output current is above
the sensing current level
(parameter P095 setting).
6
r6
Current sensing (2)
When the output current is below
the sensing current level
(parameter P095 setting).
7
r7
Fault alarm (1)
During fault trip occurrence in the
inverter.
8
r8
Fault alarm (2)
When the inverter is in normal
status (OFF for fault trip status).
Содержание VF200
Страница 1: ...VF200 WME VF200 A 2013 01 panasonic net id pidsx global ...
Страница 2: ......
Страница 7: ......
Страница 8: ...1 Safety Precautions ...
Страница 14: ...Safety Precautions 7 7 Warning Label on Inverter VF200 ...
Страница 15: ...Safety Precautions 8 ...
Страница 16: ...9 Points for Handling Special Precautions 10 ...
Страница 19: ...Points for Handling ...
Страница 20: ...13 1 Parts Identification 1 1 Part Names and Functions 14 1 2 Details on Part Number 16 ...
Страница 29: ...2 Installation 22 VF200 ...
Страница 49: ...42 ...
Страница 56: ...4 Operation Method Basic Operation ...
Страница 66: ...4 Operation Method Basic Operation 7 Stop operation Press button The motor starts to decelerate till to stop ...
Страница 75: ...4 Operation Method Basic Operation ...
Страница 76: ...69 5 Control Status Monitor 5 1 List of Control Status Monitor Items 70 5 2 Introduction of Monitor No 72 ...
Страница 88: ...81 6 Function Parameters 6 1 Setting and Changing Function Parameters 8 6 2 Function Parameter List 83 ...
Страница 101: ...6 Function Parameters 94 ...
Страница 102: ...95 7 Custom Mode 7 1 Allocating Parameter No 96 7 2 Setting and Changing Parameters 98 ...
Страница 107: ...7 Custom Mode 100 ...
Страница 119: ...8 Setting Mode and Copy Function of Built in Memory 112 ...
Страница 126: ...9 Troubleshooting 119 9 3 3 Breaker Trip 9 3 4 Motor Overheating 9 3 5 Communication Failed ...
Страница 127: ...9 Troubleshooting 120 ...
Страница 136: ...129 11 Specifications 11 1 Rated Specifications 130 11 2 Standard Specifications 132 11 3 Common Specifications 133 ...
Страница 145: ...11 Specifications 138 ...
Страница 146: ...139 Appendix Function Parameter List ...
Страница 208: ...Appendix Function Parameter List 201 ...