Appendix Function Parameter List
256
P143
Cooling Fan ON-OFF Control Select
・
Operation modes of cooling fan in normal status and fault status can be set.
Details
Setting
value
Operation of cooling fan
Operation when heat sink
is faulty
0
Power-on: ON
Power-off :OFF
The inverter stops
abnormally.
1
Power-on: ON
Heat sink temperature is
below 100
℃
: OFF
The inverter stops
abnormally.
2
Power-on: ON
Power-off :OFF
The inverter does not stop
but sends out alarm.
3
Power-on: ON
Heat sink temperature is
below 100
℃
: OFF
The inverter does not stop
but sends out alarm.
・
The parameter is invalid to models without cooling fan (1-phase 200 V/ 0.2 to
0.75 kW model and 3-phase 400 V/0.75 kW model).
P144
Input Terminal Filter
Filter constant of control circuit terminals (No.2 to No.8) can be set in the
inverter to effectively remove interference of external signal input.
Setting value (times)
5 to 100 (Increment = 1)
・
If the setting value is too high, the interference resistance capability will be
enhanced, but response speed of control input terminals will decrease.
・
If the setting value is too low, the interference resistance capability will be
weakened, but response speed of control input terminals will increase.
・
When start/stop, forward run and reverse run signal (terminal No.2 and No.3)
are used to operate the inverter, internal processing time of the inverter will
become longer even if the setting value is low. In this case, response speed of
control input terminals will be slower than other terminals.
Содержание VF200
Страница 1: ...VF200 WME VF200 A 2013 01 panasonic net id pidsx global ...
Страница 2: ......
Страница 7: ......
Страница 8: ...1 Safety Precautions ...
Страница 14: ...Safety Precautions 7 7 Warning Label on Inverter VF200 ...
Страница 15: ...Safety Precautions 8 ...
Страница 16: ...9 Points for Handling Special Precautions 10 ...
Страница 19: ...Points for Handling ...
Страница 20: ...13 1 Parts Identification 1 1 Part Names and Functions 14 1 2 Details on Part Number 16 ...
Страница 29: ...2 Installation 22 VF200 ...
Страница 49: ...42 ...
Страница 56: ...4 Operation Method Basic Operation ...
Страница 66: ...4 Operation Method Basic Operation 7 Stop operation Press button The motor starts to decelerate till to stop ...
Страница 75: ...4 Operation Method Basic Operation ...
Страница 76: ...69 5 Control Status Monitor 5 1 List of Control Status Monitor Items 70 5 2 Introduction of Monitor No 72 ...
Страница 88: ...81 6 Function Parameters 6 1 Setting and Changing Function Parameters 8 6 2 Function Parameter List 83 ...
Страница 101: ...6 Function Parameters 94 ...
Страница 102: ...95 7 Custom Mode 7 1 Allocating Parameter No 96 7 2 Setting and Changing Parameters 98 ...
Страница 107: ...7 Custom Mode 100 ...
Страница 119: ...8 Setting Mode and Copy Function of Built in Memory 112 ...
Страница 126: ...9 Troubleshooting 119 9 3 3 Breaker Trip 9 3 4 Motor Overheating 9 3 5 Communication Failed ...
Страница 127: ...9 Troubleshooting 120 ...
Страница 136: ...129 11 Specifications 11 1 Rated Specifications 130 11 2 Standard Specifications 132 11 3 Common Specifications 133 ...
Страница 145: ...11 Specifications 138 ...
Страница 146: ...139 Appendix Function Parameter List ...
Страница 208: ...Appendix Function Parameter List 201 ...