5.4. Setting Filters (Tuning Level 2)
2) Keep pressing the (–) key several times to lower the frequency of low-pass filter (FP setting) until
rotation of noise of the Motor decreases.
[+],[-],[ENT]
333( 222)
STEP10
_FP500
-
+
-
+
• • •
3) If motion of the Motor becomes unstable press the (+) key several times to increase the low-pass
filter frequency (FP setting) until it becomes stable.
Pressing ,
[+],[-],[ENT]
233( 123)
STEP1
_FP120
SHIFT
-
+
-
+
• • •
4) Press the ENT to complete the setting.
233( 123)
STEP1
FP120
:_
ENT
[Reference] When terminate the low-pass filter:
:FP0
:_
ENT
P 0
?
F
[Reference] Adjusting notch filter
l
When setting the notch filters (NP and NS), you need to measure the resonant frequency by
checking voltage between the analog velocity monitor pins (VELOCITY-GND terminals) on the
front panel of Driver by means of an oscilloscope, etc.
à
Check the resonant frequency as show in Figure5-3. If the frequency is 200 Hz, type as
0
?
P
2
$
N
ENT
0
?
to set the notch filter to 200 Hz.
Figure 5-3: Measuring resonant frequency
Display
200Hz (5ms)
:NP200
:_
Oscilloscope
Содержание MEGATORQUE M-ESB-YSB2020AB300
Страница 2: ...MEGATORQUE MOTOR SYSTEM User s Manual ESB Driver Unit System EC T Document Number C20140 01 ...
Страница 7: ... Blank Page ...
Страница 11: ... iv Blank Page ...
Страница 295: ... 8 66 B B3 3 t ty yp pe e B B5 5 t ty yp pe e 8 2 Parameter List 2 23 3 t ty yp pe e 2 25 5 t ty yp pe e Blank page ...
Страница 355: ...1st Edition 1st Printing November 20 2003 Document Number C20140 01 ...