8 Additional Information
BU 0200 GB
Subject to technical alterations
171
8.3.2
Reduced overcurrent due to time
The possible overload capacity changes depending on the duration of an overload. Several values are cited
in this table. If one of these limiting values is reached, the frequency inverter must have sufficient time (with
low utilisation or without load) in order to regenerate itself.
If operated repeatedly in the overload region at short intervals, the limiting values stated in the tables are
reduced.
230V devices:
Reduced overload capacity (approx.) due to pulse frequency (P504) and time
Pulse frequency [kHz]
Time [s]
> 600
60
30
20
10
3.5
3...8
110% 150% 170% 180% 180% 200%
10
103% 140% 155% 165% 165% 180%
12
96% 130% 145% 155% 155% 160%
14
90% 120% 135% 145% 145% 150%
16
82% 110% 125% 135% 135% 140%
400V devices:
Reduced overload capacity (approx.) due to pulse frequency (P504) and time
Pulse frequency [kHz]
Time [s]
> 600
60
30
20
10
3.5
3...6
110% 150% 170% 180% 180% 200%
8
100% 135% 150% 160% 160% 165%
10
90% 120% 135% 145% 145% 150%
12
78% 105% 120% 125% 125% 130%
14
67% 92% 104% 110% 110% 115%
16
57% 77% 87% 92% 92% 100%