Parameter
[factory setting]
Setting value / Description / Note
Device
Supervisor
Parameter
set
P410
Minimum frequency auxiliary
setpoints
P
-400.0 ... 400.0 Hz
[ 0.0 ]
The minimum frequency that can act on the setpoint via the auxiliary setpoints.
Auxiliary setpoints are all frequencies which are additionally supplied for further functions in the FI:
Frequency
addition
Frequency
subtraction
Auxiliary setpoints via BUS
PID Process controller
PID
controller
Multiplication
P411
Maximum frequency auxiliary
setpoints
P
-400.0 ... 400.0 Hz
[ 50.0 ]
The minimum frequency that can act on the setpoint via the auxiliary setpoints.
Auxiliary setpoints are all frequencies which are additionally delivered for further functions in the FI:
Frequency
addition
Frequency
subtraction
Auxiliary setpoints via BUS
PID process controller
PID
controller
Multiplication
P412
Process controller setpoint
S
P
-10.0 ... 10.0 V
[ 5.0 ]
Fixed specification of a setpoint for the process controller that will only occasionally be altered.
Only with P400 = 6 or 7 (PID process controller). Further details can be found in Chap. 8.2
P413
PID control P-component
S
P
0.0 ... 400.0 %
[ 10.0 ]
This parameter is only effective when the function PID controller actual frequency is selected.
The P-component of the PID controller determines the frequency jump if there is a control
deviation based on the control difference.
For example: At a setting of P413 = 10% and a rule difference of 50%, 5% is added to the
actual setpoint.
P414
PI control I-component
S
P
0.0 ... 3000.0 %/s
[ 10.0 ]
This parameter is only effective when the function PID controller actual frequency is selected.
In case of a control deviation, the I-component of the PID controller determines the frequency
change, dependent on time.
P415
Process controller control limit
S
P
0 ... 400.0 %
[ 10.0 ]
This parameter is only effective when the
function PID process controller
is selected.
For further details, see Section 8.2.
P416
PID controller ramp time
S
P
0.00 ... 99.99 s
[ 2.00 ]
This parameter is only effective when the function PID actual frequency is selected.
Ramp for PI setpoint
P417
Offset analog output 1
S
P
-10.0 ... 10.0 V
[ 0.0 ]
In the analog output function an offset can be entered to simplify the processing of the analog
signal in other equipment.
If the analog output has been programmed with a digital function, then the difference between
the switch-on point and the switch-off point can be set in this parameter (hysteresis).
... only with
SK CU4-IOE or
SK TU4-IOE
Содержание NORDAC SK 200E
Страница 2: ...NORDAC SK 200E Manual 2 BU 0200 GB...
Страница 35: ...2 Mounting and Installation BU 0200 GB Subject to technical alterations 35...
Страница 60: ...NORDAC SK 200E Manual 60 Subject to technical alterations BU 0200 GB...
Страница 151: ...5 9 Overview of Parameters User defined Settings BU 0200 GB Subject to technical alterations 151...