Parameter
[factory setting]
Setting value / Description / Note
Device
Supervisor
Parameter
set
P419
Standardisation analog output 1
S
P
-500 ... 500 %
[ 100 ]
Using this parameter an adjustment can be made to the analog output for the selected operating
zone. The maximum analog output (10V) corresponds to the standardisation value of the
appropriate selection.
If therefore, at a constant working point, this parameter is raised from 100% to 200%, the analog
output voltage is halved. 10 Volt output signal then corresponds to twice the nominal value.
For negative values the logic is reversed. A setpoint value of 0% will then produce 10V at the
output and -100% will produce 0V.
... only with
SK CU4-IOE or
SK TU4-IOE
P420
[-
01]
...
[-
04]
Digital inputs 1 to 4
0 ... 72
[ -01 = 1 ]
[ -02 = 2 ]
[ -03 = 4 ]
[ -04 = 5 ]
In the SK 200E, up to 4 freely programmable digital inputs are available. The only
restriction is with the versions SK 215E and SK 235E. Here, the fourth digital input is
always the input for the function “Safe Stop”.
[-01] = Digital input 1
(DIN1)
, Enable right
as factory setting, control terminal 21
[-01] = Digital input 2
(DIN1)
, Enable left
as factory setting, control terminal 22
[-03] = Digital input 3
(DIN3)
, Fixed frequency 1
(P465 [-01]) as factory setting, control terminal 23
[-04] = Digital input 4
(DIN4)
, Fixed frequency 2
(P465 [-02]) as factory setting,
not with SK 215/235E
”Safe Stop”, control terminal 24
Various functions can be programmed. These can be seen in the following table.
Содержание NORDAC SK 200E
Страница 2: ...NORDAC SK 200E Manual 2 BU 0200 GB...
Страница 35: ...2 Mounting and Installation BU 0200 GB Subject to technical alterations 35...
Страница 60: ...NORDAC SK 200E Manual 60 Subject to technical alterations BU 0200 GB...
Страница 151: ...5 9 Overview of Parameters User defined Settings BU 0200 GB Subject to technical alterations 151...