8 Additional Information
BU 0200 GB
Subject to technical alterations
173
8.3.4
Reduced output current due to mains voltage
The devices are designed with thermal characteristics according to the nominal output currents.
Accordingly, for lower mains voltages, higher currents cannot be taken off in order to maintain the stated
power constant. For mains voltages above 400v there is a reduction of the permissible continuous output
current, which is inversely proportional to the mains voltage, in order to compensate for the increased
switching losses.
1.2
0.4
k Unetz Unetz
(
)
480
320
Une tz
320
340
360
380
400
420
440
460
480
0.4
0.5
0.6
0.7
0.8
0.9
1
1.1
1.2
Mains voltage [V]
I / I
N
8.3.5
Reduced output current due to the heat sink temperature
The temperature of the heat sink in included in the calculation of the reduction of output current, so that at
low heat sink temperatures, a higher load capacity can be permitted, especially for higher pulse frequencies.
At high heat sink temperatures, the reduction is increased correspondingly. The ambient temperature and
the ventilation conditions for the device can therefore be optimally exploited.