6 Error Messages
BU 0200 GB
Subject to technical alterations
155
Anzeige in der
SimpleBox
Error
text in the Parameter Box
Cause
Remedy
Group
Detail in
P700 / P701
E010
10.0
Telegram downtime / Bus off
24V int. CANbus
Data transfer is faulty. Check P513.
Check external bus connection.
Check bus protocol program process.
Check Bus master.
Check 24V supply of internal CAN/CANopen Bus.
Nodeguarding
error (internal CANopen)
Bus Off
error (internal CANbus)
10.2
External bus module
telegram time-out
Telegram transfer is faulty.
Check external connection.
Check Bus Protocol program process.
Check Bus master.
10.4
External bus module
initialisation failure
Check P746.
Bus module not correctly plugged in.
Check Bus module current supply.
10.1
External Bus module system
failure
Further details can be found in the respective additional
BUS operating instructions.
10.3
10.5
10.6
10.7
10.8 External
module
communication failure
Connection fault / error in the external component
10.9 Missing
module
Module entered in P120 is not available.
E011
11.0 Customer
Unit
ADU
(analog/digital converter
error)
Internal Customer Unit (internal data bus) faulty or disturbed
by radio emissions (EMC).
Check control terminals connection for short-circuit.
Minimise EMC interference through separate laying of
control and power cables.
Device and shielding must be well earthed.
Содержание NORDAC SK 200E
Страница 2: ...NORDAC SK 200E Manual 2 BU 0200 GB...
Страница 35: ...2 Mounting and Installation BU 0200 GB Subject to technical alterations 35...
Страница 60: ...NORDAC SK 200E Manual 60 Subject to technical alterations BU 0200 GB...
Страница 151: ...5 9 Overview of Parameters User defined Settings BU 0200 GB Subject to technical alterations 151...