Anzeige in der
SimpleBox
Error
text in the Parameter Box
Cause
Remedy
Group
Detail in
P700 / P701
E012
12.0
Watchdog customer /
customer error
The Watchdog function is selected at a digital input and the
impulse at the corresponding digital input is not present for
longer than the time set in parameter P460 >Watchdog
time<.
12.1
Drive switch-off limit
exceeded
The drive switch-off limit P534 [01] has triggered.
Reduce load on motor
Set a higher value in P534 [01].
12.2
Generator switch-off limit
exceeded
The generator switch-off limit P534 [02] has triggered.
Reduce load on motor
Set a higher value in P534 [02].
12.3
Torque current limit
Limit from potentiometer or setpoint source has switched off.
P400 = 12
12.4 Current
limit
Limit from potentiometer or setpoint source has switched off.
P400 = 14
E013
13.0 Encoder
error
No signal from encoder
Check 5V sensor if available.
Check supply voltage of encoder.
13.1
Speed slip error
The slip speed error limit was reached.
Increase setting in P327.
13.2
Slip error switch-off
monitoring
The slip error monitoring was triggered; the motor could not
follow the setpoint.
Check motor data P201-P209! This data is very important
for the current controller.
Check motor circuit.
If necessary, check the encoder setting P300 and the
following parameters in Servo mode.
Increase setting value for torque limit in P112.
Increase setting value for current limit in P536.
E016
16.0
Motor phase error
A motor phase is not connected.
Check P539
Check motor connections
16.1 Motor
current
monitoring for
braking mode
Required exciting current not achieved at moment of switch-on.
Check P539
Check motor connections
Содержание NORDAC SK 200E
Страница 2: ...NORDAC SK 200E Manual 2 BU 0200 GB...
Страница 35: ...2 Mounting and Installation BU 0200 GB Subject to technical alterations 35...
Страница 60: ...NORDAC SK 200E Manual 60 Subject to technical alterations BU 0200 GB...
Страница 151: ...5 9 Overview of Parameters User defined Settings BU 0200 GB Subject to technical alterations 151...