116
Subject to technical alterations BU
0200
GB
Parameter
[factory setting]
Setting value / Description / Note
Device
Supervisor
Parameter
set
P426
Quick stop time
S
P
0 ... 320.00 s
[ 0.10 ]
Setting of the stop time for the fast stop function that can be triggered either via a digital input,
the bus control, the keyboard or automatically in case of a fault.
Emergency stop time is the time for the linear frequency decrease from the set maximum
frequency (P105) to 0Hz. If an actual setpoint <100% is being used, the emergency stop time is
reduced correspondingly.
P427
Emergency stop during error
S
0 ... 2
[ 0 ]
Activation of automatic emergency stop following error
0 = OFF:
Automatic emergency stop following error is deactivated
1 =
reserved
2 = ON on error:
Automatic emergency stop following fault
P428 Automatic
starting
S
P
0 ... 1
[ 0 ]
In the standard setting (P428 =
0
Off
) the inverter requires a flank for enable (signal change
from "low
high") at the applicable digital input.
In the setting
On
1
the FI reacts to a high level. This function is only possible if the FI is
controlled using the digital inputs. (see P509=0/1)
In certain cases, the FI must start up directly when the mains are switched on. This means that
P428 =
1
On
can be set. If the enable signal is permanently switched on, or equipped with a
cable jumper, the FI starts up immediately.
Содержание NORDAC SK 200E
Страница 2: ...NORDAC SK 200E Manual 2 BU 0200 GB...
Страница 35: ...2 Mounting and Installation BU 0200 GB Subject to technical alterations 35...
Страница 60: ...NORDAC SK 200E Manual 60 Subject to technical alterations BU 0200 GB...
Страница 151: ...5 9 Overview of Parameters User defined Settings BU 0200 GB Subject to technical alterations 151...