5.5 Control Terminals
BU 0200 GB
Subject to technical alterations
107
5.5 Control terminals
Parameter
[factory setting]
Setting value / Description / Note
Device
Supervisor
Parameter
set
P400
[-
01]
...
[-
07]
Setpoint input function
P
0 ... 17
[-01 = 1 ]
[-02 = 15 ]
[-03 = 0 ]
[-04 = 0 ]
[-05 = 1 ]
[-06 = 0 ]
[-07 = 1 ]
[-01] =
Potentiometer 1
, function of the potentiometer integrated in the FI (Section. 4.1.3).
The DIP switches 4/5 must be set to “off” (Section 4.1.1) in order for the function to
be influence by this parameter setting.
[-02] =
Potentiometer 2
, function of the potentiometer integrated in the FI (Section. 4.1.3).
The DIP switches 4/5 must be set to “off” (Section 4.1.1) in order for the function to
be influence by this parameter setting.
[-03] =
External analog input 1,
current value AIN1 of the I/O extension.
[-04] =
External analog input 2,
current value AIN2 of the I/O extension.
[-05] =
Setpoint module
, in preparation
[-06] =
Digital input 2,
can be set to impulse signal evaluation via the parameter P421=26
or 27. The impulses can then be evaluated as an analog signal in the FI, according
to the function in parameter P400 [-06].
[-07] =
Digital input 3,
can be set to impulse signal evaluation via the parameter P422=26
or 27. The impulses can then be evaluated as an analog signal in the FI, according
to the function in parameter P400 [-07].
... The setting values follow on the next page.
Содержание NORDAC SK 200E
Страница 2: ...NORDAC SK 200E Manual 2 BU 0200 GB...
Страница 35: ...2 Mounting and Installation BU 0200 GB Subject to technical alterations 35...
Страница 60: ...NORDAC SK 200E Manual 60 Subject to technical alterations BU 0200 GB...
Страница 151: ...5 9 Overview of Parameters User defined Settings BU 0200 GB Subject to technical alterations 151...