7 Technical Data
BU 0200 GB
Subject to technical alterations
165
Size 2
Size 3
Device type:
SK 2xxE…
-301-340-A
-401-340-A
-551-340-A
-751-340-A
Nominal motor power
(4-pole standard motor)
400V
3.0 kW
4.0 kW
5.5 kW
7.5 kW
480V
4 hp
5 hp
7½ hp
10 hp
Mains voltage
3 AC 380 ... 480V, -20% / +10%, 47 ... 63 Hz
Output voltage
3 AC 0 - Mains voltage
Nominal output current at
400V
rms [A]
7.5
9.5
12.5
16.0
Min. braking resistor
110
110
68
68
Recommended braking
resistor
Section
2.3.1
200
200
200
200
Ω
Typical input current at
400V
rms [A]
7.0
8.3
11.7
15.0
Rec. mains fuse
slow-
blowing [A]
16 16 20 25
Maximum continuous power:
motor-mounted (ventilated)
S1-50°C
S1-40°C, S3-50°C 70%ED 10min
3.0 kW
4.0 kW
5.5 kW
7.5 kW
Maximum continuous power:
wall-mounted (unventilated)
S1-50°C
S1-40°C, S3-50°C 70%ED 10min
S1-30°C, S3-40°C 70%ED 10min
2.2 kW
3.0 kW
4.0 kW
4.0 kW
5.5 kW
7.5 kW