3.3 Internal Customer Unit
BU 0200 GB
Subject to technical alterations
65
3.3.4
DeviceNet Module, SK CU4-DEV
Bus module for the control, parameterisation and diagnosis of up to four frequency inverters via DeviceNet.
•
Baud rate: Max. 500 kBaud
•
Protocol: AC-Drive and NORD-AC Protocol
•
2x digital inputs
•
Address and baud rate via DIP switch
•
Status LED: BG status, BG fault, DIN1, DIN2,
Bus status, Bus fault
•
Details in Bus Manual BU 0250 (www.nord.com)
Module
SK CU4-DEV
Function
Pin
Labelling
1
44
+24V, external 24 V supply
External supply voltage for the module,
24V ±20%,
≤
150mA
2
40
GND reference potential
3
C1
BDIN1 / digital input 1
Digital inputs, SPS-compatible as per EN61131-2,
low: 0-5V, high: 11-30V
…, used for further processing via the bus.
4
C2
BDIN2 / digital input 2
5
77
SYS+, system bus
System bus connection to FI
6
78
SYS-, system bus
7
40
GND, reference potential
External, galvanically isolated supply voltage for
DeviceNet, 24V ±20%,
≤
150mA
8
45
+24VB, external galvanically
isolated 24V bus supply
Electrical isolation
9
75
CAN+, DeviceNet
DeviceNet data cable for external communication,
incoming
10
76
CAN-, DeviceNet
11
46
GNDB, Bus Ground
Bus reference potential
12
90
SHLD, Shield
Data cable shielding
13
45
+24VB, external galvanically
isolated 24V bus supply
External, galvanically isolated supply voltage for the
CANopen bus, 24V ±20%,
≤
150mA
14
75
CAN+, DeviceNet
DeviceNet data cable for external communication,
outgoing
15
76
CAN-, DeviceNet
16
46
GNDB, Bus Ground
Bus reference potential
Содержание NORDAC SK 200E
Страница 2: ...NORDAC SK 200E Manual 2 BU 0200 GB...
Страница 35: ...2 Mounting and Installation BU 0200 GB Subject to technical alterations 35...
Страница 60: ...NORDAC SK 200E Manual 60 Subject to technical alterations BU 0200 GB...
Страница 151: ...5 9 Overview of Parameters User defined Settings BU 0200 GB Subject to technical alterations 151...