GB
5.3 Motor data / characteristic curve parameters
Parameter
[factory setting]
Setting value / Description / Note
Device
Supervisor
Parameter
set
P200 Motor
list
P
0 ... 45
[ 0 ]
The factory settings for the motor data can be edited with this parameter. The factory setting in
parameters P201...P209 is a 4-pole DS standard motor with the nominal FI power setting.
By selecting one of the possible digits and pressing the OK key, all motor parameters
(P201…P209) are adjusted to the selected standard power. The basis for the motor data is a 4-
pole DS standard motor
0 =
No change to data
1 = No motor:
In this setting, the FI operates without current control, slip compensation and
pre-magnetising time, and is therefore not recommended for motor applications. Possible
applications are induction furnaces or other applications with coils and transformers. The
following motor data is set here:
50.0Hz / 1500rpm / 15.0A / 400V / 0.00kW / cos
=0.90 / Star / R
S
0,01
/ I
EMPTY
6.5A
2 =
0.25kW 230V
3 =
0.33Hp 230V
4 =
0.25kW 400V
5 =
0.33Hp 460V
6 =
0.37kW 230V
7 =
0.50HP = 230V
8 =
0.37kW 400V
9 =
0.50HP = 460V
10 =
0.55kW 230V
11 =
0.75Hp 230V
12 =
0.55kW 400V
13 =
0.75Hp 460V
14 =
0.75kW 230V
15 =
1.0PS 230V
16 =
0.75kW 400V
17 =
1.0PS 460V
18 =
1.1kW 230V
19 =
1.5PS 230V
20 =
1.1kW 400V
21 =
1.5PS 460V
22 =
1.5kW 230V
23 =
2.0PS 230V
24 =
1.5kW 400V
25 =
2.0PS 460V
26 =
2.2kW 230V
27 =
3.0PS 230V
28 =
2.2kW 400V
29 =
3.0PS 460V
30 =
3.0kW 230V
31 =
3.0kW 400V
32 =
4.0kW 230V
33 =
5.0PS 230V
34 =
4.0kW 400V
35 =
5.0PS 460V
36 =
5.5kW 230V
37 =
7.5PS 230V
38 =
5.5kW 400V
39 =
7.5PS 460V
40 =
7.5kW 230V
41 =
10PS 230V
42 =
7.5kW 400V
43 =
10PS 460V
44 =
11kW 400V
45 =
15PS 460V
NOTE:
As P200 returns to = 0 after the input confirmation, the control of the set motor can
be implemented via parameter P205.
If DIP switch 7 (50/60Hz operation, Section 4.1.1) is switched over, the appropriate
nominal motor data according to the FI power rating are reloaded from the P200 list.
P201 Nominal
frequency
S
P
10.0 ... 400.0 Hz
[
]
The motor nominal frequency determines the V/f break point at which the FI supplies the
nominal voltage (P204) at the output.
P202 Nominal
speed
S
P
150 ... 24000 rpm
[***]
The nominal motor speed is important for the correct calculation and control of the motor slip
and the speed display (P001 = 1).
P203 Nominal
current
S
P
0.1 ... 300.0 A
[***]
The nominal motor current is a decisive parameter for the current vector control.
***
These settings are dependent on the nominal power of the FI or the selection in parameter P200.
Содержание NORDAC SK 200E
Страница 2: ...NORDAC SK 200E Manual 2 BU 0200 GB...
Страница 35: ...2 Mounting and Installation BU 0200 GB Subject to technical alterations 35...
Страница 60: ...NORDAC SK 200E Manual 60 Subject to technical alterations BU 0200 GB...
Страница 151: ...5 9 Overview of Parameters User defined Settings BU 0200 GB Subject to technical alterations 151...