4 Commissioning
BU 0200 GB
Subject to technical alterations
87
4.2 Factory settings
All frequency inverters supplied by Getriebebau NORD are pre-programmed with the default setting for
standard applications with 4 pole standard motors (same voltage and power). For use with motors with
other powers or number of poles, the data from the rating plate of the motor must be input into the
parameters P201...P207 under the menu item >Motor data< <.
NOTE:
All motor data can be pre-set using the parameter P200. After use of this function has been
successful, this parameter is reset to
0 = no change
! The data is loaded automatically into
parameters P201...P209 – and can be compared again with the data on the motor rating
plate.
3~ Mot
IEC 56
IM B3
cos
0,74
cos
0,74
IP55
Rot. KL 16
Th.Cl.F
EN60034
60 Hz
460 V Y
5,2 A
2,5 kW
1765 /min
1440 /min
P206
P201
P204
P203 P202
P200
9,0 /
5,2 A
50 Hz
2,2 kW
P207
P200 Motor list:
0 = no changes
8 = 0.37kW 400V
1 = no motor
9 = 0.50PS 460V
2 = 0.25kW 230V
10 = 0.55kW 230V
3 = 0.33PS 230V
11 = 0.75PS 230V
4 = 0.25kW 400V
12 = 0.55kW 400V
5 = 0.33PS 460V
13 = 0.75PS 460V
6 = 0.37kW 230V
14 = 0.75kW 230V
7 = 0.50PS 230V ....
230 /
400 V
/
Y
RECOMMENDATION:
For the correct operation of the drive unit, it is necessary to input the motor data
according to the rating plate as precisely as possible. In particular, an automatic
stator resistance measurement using parameter P220 is recommended.
In order to automatically determine the stator resistance, P220 = 1 must be set and
confirmed by pressing "OK". The value calculated for the line resistance
(dependent upon P207) will be saved in P208.
Содержание NORDAC SK 200E
Страница 2: ...NORDAC SK 200E Manual 2 BU 0200 GB...
Страница 35: ...2 Mounting and Installation BU 0200 GB Subject to technical alterations 35...
Страница 60: ...NORDAC SK 200E Manual 60 Subject to technical alterations BU 0200 GB...
Страница 151: ...5 9 Overview of Parameters User defined Settings BU 0200 GB Subject to technical alterations 151...