5.5 Control Terminals
BU 0200 GB
Subject to technical alterations
119
Parameter
[factory setting]
Setting value / Description / Note
Device
Supervisor
Parameter
set
P464
Fixed frequency mode
S
0 ... 1
[ 1 ]
This parameter determines the handling of fixed frequencies. With addition, simultaneously
controlled values are added together. Otherwise, each value is output separately, whereby with
multiple control the highest frequency value is always output.
0 =
Addition to setpoint value
1 =
No addition / fixed frequency is setpoint value
P465
… - 01
...
... - 15
Fixed frequency / Array
-400.0 ... 400.0 Hz
[ -01 = 5.0 ]
[ -02 = 10.0 ]
[ -03 = 20.0 ]
[ -04 = 35.0 ]
[ -05 = 50.0 ]
[ -06 = 70.0 ]
[ -07 = 100.0 ]
[ -08 = 0.0 ]
[ -09 = -5.0 ]
[ -10 = -10.0 ]
[ -11 = -20.0 ]
[ -12 = -35.0 ]
[ -13 = -50.0 ]
[ -14 = -70.0 ]
[ -15 = -100.0 ]
In the array levels, up to 31 different fixed frequencies can be set, which in turn can be encoded
for the functions 50…54 in binary code for the digital inputs.
[-01] =
Fixed frequency 1 / Array 1
[-02] =
Fixed frequency 2 / Array 2
[-03] =
Fixed frequency 3 / Array 3
[-04] =
Fixed frequency 4 / Array 4
[-05] =
Fixed frequency / Array 5
[-06] =
Fixed frequency / Array 6
[-07] =
Fixed frequency / Array 7
[-08] =
Fixed frequency / Array 8
[-09] =
Fixed frequency / Array 9
[-10] =
Fixed frequency / Array 10
[-11] =
Fixed frequency / Array 11
[-12] =
Fixed frequency / Array 12
[-13] =
Fixed frequency / Array 13
[-14] =
Fixed frequency / Array 14
[-15] =
Fixed frequency / Array 15
P466
Minimum frequency process
controller
S
P
-400.0 ... 400.0 Hz
[ 0.0 ]
With the aid of the minimum frequency process controller the control ratio can also be kept to a
minimum ratio, even with a master value of “zero”, in order to enable adjustment of the
compensator. Further details in P400 and Section 8.2.
P475
… - 01
...
... - 04
Switch on/off delay
S
-30.000 ... 30,000 s
[ 0.000 ]
Adjustable switch-on/switch-off delay for the digital inputs. Use as a switch-on filter or simple
process control is possible.
[-01] =
Digital input 1
[-02] =
Digital input 2
[-03] =
Digital input 3
[-04] =
Digital input 4
Positive values =
switch-on delayed
Negative values =
switch-off delayed
Содержание NORDAC SK 200E
Страница 2: ...NORDAC SK 200E Manual 2 BU 0200 GB...
Страница 35: ...2 Mounting and Installation BU 0200 GB Subject to technical alterations 35...
Страница 60: ...NORDAC SK 200E Manual 60 Subject to technical alterations BU 0200 GB...
Страница 151: ...5 9 Overview of Parameters User defined Settings BU 0200 GB Subject to technical alterations 151...