3.2 External Control Unit
BU 0200 GB
Subject to technical alterations
57
Parameter
Setting value / Description / Note
P1306
Box password
If the >Password< function is to be reset, the password selected in the >Set Password<
parameter must be entered here. If the correct password is selected, all of the
ParameterBox functions and the parameters of the connected frequency inverter can be
used again.
NOTE:
With the master-password ‘65’ the current password is displayed and can be
confirmed with the OK key.
P1307
Reset Box parameter
In this parameter the ParameterBox can be reset to the default setting. All ParameterBox
settings and the data in the storage media will be deleted.
P1308
Software version
Displays the software version of the ParameterBox. In case of service enquiries by
telephone, please have this at hand.
3.2.4
ParameterBox error messages
Display
Error
Cause
Remedy
Communication
error
200
INCORRECT PARAMETER NUMBER
These error messages are due to EMC interferences or differing software
versions of the participants.
Check the software version of the ParameterBox and that of the
connected frequency inverter.
Check the cabling of all components, regarding possible EMC
interference
201
PARAMETER VALUE CANNOT BE
CHANGED
202
PARAMETER OUTSIDE VALUE
RANGE
203
FAULTY SUB INDEX
204
NO ARRAY PARAMETERS
205
WRONG PARAMETER TYPE
206
INCORRECT RESPONSE
RECOGNITION USS INTERFACE
207
USS INTERFACE CHECKSUM
ERROR (RS485)
Communication between frequency inverter and ParameterBox is faulty
(EMC), safe operation cannot be guaranteed.
Check the connection to the frequency inverter. Use a shielded cable
between the devices. Route the BUS leads separately from the motor
cables.
208
FAULTY STATUS RECOGNITION
USS INTERFACE (RS485)
Communication between frequency inverter and ParameterBox is faulty
(EMC), safe operation cannot be guaranteed.
Check the connection to the frequency inverter. Use a shielded cable
between the devices. Route the BUS leads separately from the motor
cables.
209_1
INVERTER DOES NOT RESPOND
The ParameterBox is waiting for a response from the connected frequency
inverter. The waiting time has elapsed without a response being received.
Check the connection to the frequency inverter. The settings of the USS
parameters for the frequency inverter were changed during operation.
Содержание NORDAC SK 200E
Страница 2: ...NORDAC SK 200E Manual 2 BU 0200 GB...
Страница 35: ...2 Mounting and Installation BU 0200 GB Subject to technical alterations 35...
Страница 60: ...NORDAC SK 200E Manual 60 Subject to technical alterations BU 0200 GB...
Страница 151: ...5 9 Overview of Parameters User defined Settings BU 0200 GB Subject to technical alterations 151...