NORDAC SK 200E Handbuch
126
Subject to technical alterations BU
0200
GB
Parameter
Setting value / Description / Note
Device
Supervisor
Parameter
set
P535 I
2
t motor
0 … 24
[ 0 ]
The I
2
t motor function can now be set in a differentiated manner. Up to four curves with three
different triggering times can be set. The trigger times are based on classes 5, 10 and 20 for
semiconductor switching devices.
All curves run from 0Hz to half of the nominal motor frequency (P201). The full nominal current
is available from half of the nominal frequency upwards.
0 =
I
2
t monitoring is inactive
NOTE:
For switch-off classes 10 and 20, care must be taken that the FI has a sufficiently
high overload capacity.
Switch-off class 5,
60s at 1.5x I
N
Switch-off class 10,
120s at 1.5x I
N
Switch-off class 20,
240s at 1.5x I
N
I
N
at 0Hz
P535 =
I
N
at 0Hz
P535 =
I
N
at 0Hz
P535 =
100%
1
100%
9
100%
17
90%
2
90%
10
90%
18
80%
3
80%
11
80%
19
70%
4
70%
12
70%
20
60%
5
60%
13
60%
21
50%
6
50%
14
50%
22
40%
7
40%
15
40%
23
30%
8
30%
16
30%
24
P536 Current
limit
S
0.1 ... 2.0 / 2.1
(x nominal FI
current)
[ 1.5 ]
The inverter output current is limited to the set value. If this limit value is reached, the inverter
reduces the actual output frequency.
With the analog input function in P400 = 12/13, this limit value can also be varied and cause an
error message (E12.4).
0.1 ... 2.0 = Multiplier
with the inverter nominal current, gives the limit value
2.1 = OFF,
means that this limit value is disabled. The FI supplies the maximum possible
current.
Содержание NORDAC SK 200E
Страница 2: ...NORDAC SK 200E Manual 2 BU 0200 GB...
Страница 35: ...2 Mounting and Installation BU 0200 GB Subject to technical alterations 35...
Страница 60: ...NORDAC SK 200E Manual 60 Subject to technical alterations BU 0200 GB...
Страница 151: ...5 9 Overview of Parameters User defined Settings BU 0200 GB Subject to technical alterations 151...