8 Additional Information
BU 0200 GB
Subject to technical alterations
169
Device type
Max. motor cable, shielded
Jumper position
See Section
2.6.4 - 2.6.6
Cable emissions 150kHz - 30 MHz
Class A 1
C2
Class B 1
C1
SK 2x5E, motor-mounted
2 - 1
2 - 2
SK 2x5E wall-mounted
2 - 1
2 - 2
Overview of the standards, which according to product standard EN 61800-3 are applicable as testing and
measuring methods for electric drives whose speed can be altered:
Interference emission
Emission from cables
(interference voltage)
EN 55011
A 1 or C2
-
Radiated emissions
(Interference field strength)
EN 55011
A 1 or C2
-
Interference immunity
EN 61000-6-1, EN 61000-6-2
ESD, discharge of static electricity
EN 61000-4-2
6kV (CD), 8kV (AD)
EMF, high frequency electro-magnetic fields
EN 61000-4-3
10V/m; 80 - 1000MHz
Burst on control cables
EN 61000-4-4
1kV
Burst on mains and motor cables
EN 61000-4-4
2kV
Surge (phase-phase / phase-ground)
EN 61000-4-5
1kV / 2kV
Cable-led interference due to
high frequency fields
EN 61000-4-6
10V, 0.15 - 80MHz
Voltage fluctuations and drops
EN 61000-2-1
+10%, -15%; 90%
Voltage asymmetries and frequency
changes
EN 61000-2-4
3%; 2%
Wiring recommendations for mounting near to motor
M
3 ~
PE
L
1
W
V
U
W
V
U
110-1 20V
200-2 40V
380-4 80V
5 0-60Hz
L
1
L
2
PE
L
2
/N
L
3
L
3
PE
B-
B+
SK 2xxE
EMC screw connector
Brake resistor
(Accessories)
Содержание NORDAC SK 200E
Страница 2: ...NORDAC SK 200E Manual 2 BU 0200 GB...
Страница 35: ...2 Mounting and Installation BU 0200 GB Subject to technical alterations 35...
Страница 60: ...NORDAC SK 200E Manual 60 Subject to technical alterations BU 0200 GB...
Страница 151: ...5 9 Overview of Parameters User defined Settings BU 0200 GB Subject to technical alterations 151...