5.5 Control Terminals
BU 0200 GB
Subject to technical alterations
115
Value Function
Description
Signal
71
Motor potentiometer function
Fre
with automatic saving
With this motor pot. function a setpoint value (sum) is set via the
digital inputs, which is simultaneously stored. With control
enabling R/L this is then started up in the correspondingly
enabled direction. On change of direction the frequency is
retained.
Simultaneous activation of the +/- function causes the
frequency setpoint value to be set to zero.
The frequency setpoint value can also be displayed or set in the
operating value display (P001=30, current setpoint MP-S’) or in
P718.
Any minimum frequency set (P104) is still effective. Other
setpoint values, e.g. analog or fixed frequencies can be added
or subtracted.
The adjustment of the frequency setpoint value is performed
with the ramps from P102/103.
High
72
Motor potentiometer function
Frequency -
with automatic saving
High
1
If neither of the digital inputs is programmed for left or right enable, then the actuation of a fixed frequency or jog frequency will
enable the frequency inverter. The rotation field direction depends on the sign of the setpoint.
2
Also effective for Bus control (RS232, RS485, CANbus, CANopen, DeviceNet, Profibus, InterBus, AS-Interface)
Содержание NORDAC SK 200E
Страница 2: ...NORDAC SK 200E Manual 2 BU 0200 GB...
Страница 35: ...2 Mounting and Installation BU 0200 GB Subject to technical alterations 35...
Страница 60: ...NORDAC SK 200E Manual 60 Subject to technical alterations BU 0200 GB...
Страница 151: ...5 9 Overview of Parameters User defined Settings BU 0200 GB Subject to technical alterations 151...