5.6 Additional Parameters
BU 0200 GB
Subject to technical alterations
123
Parameter
Setting value / Description / Note
Device
Supervisor
Parameter
set
P510
... - 01
... - 02
Setpoint source
S
0 ... 4
[ -01 = 0 ]
[ -02 = 0 ]
Selection of the setpoint source to be parameterised.
[-01] =
Source, setpoint value
[-02] =
Source, auxiliary setpoint value
Selection of the interface via which the FI receives the setpoint.
0 = Auto:
The source of the auxiliary setpoint is
automatically derived from the setting in the
parameter P509 >Interface<
1 = Control terminals
, digital and analog inputs control
the frequency, including fixed frequencies
2 = USS
3 = System bus
4 = System bus broadcast
P511
USS Baud rate
S
0 ... 3
[ 3 ]
Setting of the transfer rate (transfer speed) via the RS485 interface. All bus participants must
have the same baud rate setting.
0 =
4800 baud
1 =
9600 baud
2 =
19200 baud
3 =
38400 baud
P512 USS
address
0 ... 30
[ 0 ]
Setting the FI Bus address.
P513 Telegram
downtime
S
-0.1 / 0.0 /
0.1 ... 100.0 s
[ 0.0 ]
Monitoring function of the active bus interface. Following receipt of a valid telegram, the next
one must arrive within the set period. Otherwise the FI reports an error and switches off with the
error message E010 >Bus Time Out<.
0.0 = Off
: Monitoring is switched off.
-0.1 = no error
: Even if communication between BusBox and FI is interrupted (e.g. 24V error,
Box removed, etc.), the FI will continue to operate unchanged.
P514
CAN baud rate (system bus)
S
0 ... 7
[ 5 ]
Setting of the transfer rate (transfer speed) via the system bus interface. All bus participants
must have the same baud rate setting.
0 =
10kBaud
1 =
20kBaud
2 =
50kBaud
3 =
100kBaud
4 =
125kBaud
5 =
250kBaud
6 =
500kBaud
7 =
1Mbaud *
*) Safe operation cannot be guaranteed
P515
... - 01
…
... - 03
CAN address (system bus)
S
0 ... 255 dec
[ alle 32 dec ]
or [ all 20 hex]
Setting of the system bus address.
[-01] =
System bus reception address
[-02] =
Broadcast – reception address for system bus (slave)
[-03] =
Broadcast – transmission address for system bus (master)
NOTE:
If up to four SK 200E are to be linked via the system bus, the addresses must be set as follows
FU1 = 32, FU2 = 34, FU3 = 36, FU4 = 38.
The system bus addresses should be set via the DIP switches 1/2 (Section 4.1.1).
Содержание NORDAC SK 200E
Страница 2: ...NORDAC SK 200E Manual 2 BU 0200 GB...
Страница 35: ...2 Mounting and Installation BU 0200 GB Subject to technical alterations 35...
Страница 60: ...NORDAC SK 200E Manual 60 Subject to technical alterations BU 0200 GB...
Страница 151: ...5 9 Overview of Parameters User defined Settings BU 0200 GB Subject to technical alterations 151...