Part 5: Review on Replacement of MR-J3-DU_ with MR-J4-DU_
5 - 42
(2) SSCNET interface 200 V/400 V class
POINT
When you connect the amplifier to a servo system controller, servo parameter
values of the servo system controller will be written to each parameter.
Setting may not be made to some parameters and their ranges depending on
the servo system controller model, drive unit software version, and MR
Configurator2 software version. For details, refer to the servo system controller
user's manual.
Here are described settings of drive unit specific parameters. Settings of the other parameters are
the same as MR-J4-_B_. Refer to "Part 3: section 3.6".
MR-J3-DU-_B_ MR-J4-DU_B_
No.
Name and function
Initial
value
No.
Name and function
Initial
value
PA02 Regenerative
option
Set this parameter when using the regenerative option,
brake unit, power regeneration converter, or power
regeneration common converter.
0 0 x x:
Selection of regenerative option
00: Regenerative option is not used, or when you use a
regenerative option, set the regenerative option with
the converter unit.
When using the drive unit with the resistance
regeneration converter unit, set this value regardless
of whether or not the regenerative option and brake
unit are used.)
0000h PA02 Regenerative
option
Select a regenerative option.
For the drive unit, select the regenerative option with the
converter unit.
Selecting other than "_ _ 0 0" or "_ _ 0 1" will trigger [AL.
37 Parameter error].
_ _ x x:
Regenerative option selection
00: Regenerative option is not used, or when you use a
regenerative option, set the regenerative option with
the converter unit.
When using the drive unit with the resistance
regeneration converter unit, set this value regardless
of whether or not the regenerative option and brake
unit are used.)
0h
_ x _ _:
Converter unit selection
0: MR-CR_
7: MR-CV_
Setting a value other than "0" or "7" will trigger [AL. 37].
0h
x _ _ _:
Enable or disable the protection coordination mode.
0: Protection coordination mode enabled
4: Protection coordination mode disabled (stand-alone
drive)
Set "4" for the drive unit which is not connected to the
MR-CV_ with the protection coordination cable.
To disable the protection coordination mode, set
"Protection coordination mode function between
converter and drive unit selection" of [Pr. PF03] to
"Enabled (_ 1 _ _)", and then this parameter to
"Protection coordination mode disabled (4 _ _ _)".
0h
Содержание Melservo MR-J3-100B
Страница 17: ...8 MEMO ...
Страница 18: ...Part 1 Summary of MR J3 MR J3W Replacement 1 1 Part 1 Summary of MR J3 MR J3W Replacement ...
Страница 145: ...Part 3 Review on Replacement of MR J3 _B_ with MR J4 _B_ 3 48 MEMO ...
Страница 146: ...Part 4 Replacement of MR J3W _B with MR J4W2 _B 4 1 Part 4 Review on Replacement of MR J3W _B with MR J4W2 _B ...
Страница 195: ...Part 4 Replacement of MR J3W _B with MR J4W2 _B 4 50 MEMO ...
Страница 196: ...Part 5 Review on Replacement of MR J3 DU_ with MR J4 DU_ 5 1 Part 5 Review on Replacement of MR J3 DU_ with MR J4 DU_ ...
Страница 277: ...Part 5 Review on Replacement of MR J3 DU_ with MR J4 DU_ 5 82 MEMO ...
Страница 278: ...Part 6 Common Reference Material 6 1 Part 6 Common Reference Material ...
Страница 418: ...Part 7 Review on Replacement of Motor 7 1 Part 7 Review on Replacement of Motor ...
Страница 564: ...Part 9 Startup Procedure Manual 9 1 Part 9 Startup Procedure Manual ...
Страница 567: ...Part 9 Startup Procedure Manual 9 4 MEMO ...
Страница 589: ...L NA 03127ENG C ...