Part 4: Replacement of MR-J3W-_B with MR-J4W2-_B
4 - 35
MR-J3W-_B MR-J4W2-_B
No.
Name and function
Initial
value
No.
Name and function
Initial
value
PB19 Vibration suppression control vibration frequency setting
This parameter cannot be used in the speed control
mode.
Set the vibration frequency for vibration suppression
control to suppress low-frequency machine vibration,
such as enclosure vibration.
When [Pr. PB02] is set to "_ _ _ 2" , this parameter can
be set manually.
100.0 PB19 Vibration
suppression
control 1 - Vibration frequency
Set the vibration frequency for vibration suppression
control 1 to suppress low-frequency machine vibration.
When "Vibration suppression control 1 tuning mode
selection" is set to "Automatic setting (_ _ _ 1)" in [Pr.
PB02], this parameter will be set automatically. When
"Manual setting (_ _ _ 2)" is selected, the setting written
to the parameter is used.
The setting range of this parameter varies, depending on
the value in [Pr. PB07]. If a value out of the range is set,
the vibration suppression control will be disabled.
100.0
PB20
Vibration suppression control resonance frequency
setting
This parameter cannot be used in the speed control
mode.
Set the resonance frequency for vibration suppression
control to suppress low-frequency machine vibration,
such as enclosure vibration.
When [Pr. PB02] is set to "_ _ _ 2" , this parameter can
be set manually.
100.0
PB20
Vibration suppression control 1 - Resonance frequency
Set the resonance frequency for vibration suppression
control 1 to suppress low-frequency machine vibration.
When "Vibration suppression control 1 tuning mode
selection" is set to "Automatic setting (_ _ _ 1)" in [Pr.
PB02], this parameter will be set automatically. When
"Manual setting (_ _ _ 2)" is selected, the setting written
to the parameter is used.
The setting range of this parameter varies, depending on
the value in [Pr. PB07]. If a value out of the range is set,
the vibration suppression control will be disabled.
100.0
PB21 This parameter is not used. Do not change the value.
0.00 PB21
Vibration
suppression
control 1 - Vibration frequency
damping
Set a damping of the vibration frequency for vibration
suppression control 1 to suppress low-frequency
machine vibration.
When "Vibration suppression control 1 tuning mode
selection" is set to "Automatic setting (_ _ _ 1)" in [Pr.
PB02], this parameter will be set automatically. When
"Manual setting (_ _ _ 2)" is selected, the setting written
to the parameter is used.
0.00
PB22 This parameter is not used. Do not change the value. 0.00
PB22
Vibration
suppression control 1 - Resonance frequency
damping
Set a damping of the resonance frequency for vibration
suppression control 1 to suppress low-frequency
machine vibration.
When "Vibration suppression control 1 tuning mode
selection" is set to "Automatic setting (_ _ _ 1)" in [Pr.
PB02], this parameter will be set automatically. When
"Manual setting (_ _ _ 2)" is selected, the setting written
to the parameter is used.
0.00
PB23 Low-pass filter selection
Select the low-pass filter.
0 0 x 0:
Low-pass filter selection
0: Automatic setting
1: Manual setting ([Pr. PB18] setting)
When automatic setting has been selected, select the
filter that has the band width close to the one calculated
with
GD2
+
1
10
VG2
・
[rad/s]
0000h
PB23 Low-pass filter selection
Select the shaft resonance suppression filter and low-
pass filter.
_ _ _ x:
Shaft resonance suppression filter selection
0: Automatic setting
1: Manual setting
2: Disabled
When you select "Enabled (_ _ _ 1)" of "Machine
resonance suppression filter 4 selection" in [Pr. PB49],
the shaft resonance suppression filter is not available.
0h
_ _ x _ :
Low-pass filter selection
0: Automatic setting
1: Manual setting
2: Disabled
0h
_ x _ _ :
For manufacturer setting
0h
x _ _ _ :
For manufacturer setting
0h
Содержание Melservo MR-J3-100B
Страница 17: ...8 MEMO ...
Страница 18: ...Part 1 Summary of MR J3 MR J3W Replacement 1 1 Part 1 Summary of MR J3 MR J3W Replacement ...
Страница 145: ...Part 3 Review on Replacement of MR J3 _B_ with MR J4 _B_ 3 48 MEMO ...
Страница 146: ...Part 4 Replacement of MR J3W _B with MR J4W2 _B 4 1 Part 4 Review on Replacement of MR J3W _B with MR J4W2 _B ...
Страница 195: ...Part 4 Replacement of MR J3W _B with MR J4W2 _B 4 50 MEMO ...
Страница 196: ...Part 5 Review on Replacement of MR J3 DU_ with MR J4 DU_ 5 1 Part 5 Review on Replacement of MR J3 DU_ with MR J4 DU_ ...
Страница 277: ...Part 5 Review on Replacement of MR J3 DU_ with MR J4 DU_ 5 82 MEMO ...
Страница 278: ...Part 6 Common Reference Material 6 1 Part 6 Common Reference Material ...
Страница 418: ...Part 7 Review on Replacement of Motor 7 1 Part 7 Review on Replacement of Motor ...
Страница 564: ...Part 9 Startup Procedure Manual 9 1 Part 9 Startup Procedure Manual ...
Страница 567: ...Part 9 Startup Procedure Manual 9 4 MEMO ...
Страница 589: ...L NA 03127ENG C ...