Part 4: Replacement of MR-J3W-_B with MR-J4W2-_B
4 - 44
MR-J3W-_B MR-J4W2-_B
No.
Name and function
Initial
value
No.
Name and function
Initial
value
PC20 This parameter is not used. Do not change the value.
0000h
PC20 Function selection C-7
Select the detection method of [AL. 10 Undervoltage].
_ _ _ x:
For manufacturer setting
0h
_ _ x _ :
For manufacturer setting
0h
_ x _ _ :
Undervoltage alarm selection
Select the alarm/alarm and warning for when the bus
voltage drops to the undervoltage alarm level.
0: [AL. 10] regardless of servo motor speed
1: [AL. E9] at servo motor speed 50 r/min (50 mm/s) or
less, [AL. 10] at over 50 r/min (50 mm/s)
0h
x _ _ _ :
For manufacturer setting
0h
PC21 Alarm history clear
Used to clear the alarm history.
0 0 0 x:
Alarm history clear
0: Invalid
1: Valid
When alarm history clear is made valid, the alarm
history is cleared at next power-on.
After the alarm history is cleared, the setting is
automatically made invalid (reset to 0).
0000h
PC21 Alarm history clear
Used to clear the alarm history.
_ _ _ x:
Alarm history clear selection
0: Disabled
1: Enabled
When "Enabled" is set, the alarm history will be cleared
at the next power-on. Once the alarm history is cleared,
the setting becomes disabled automatically.
0h
_ _ x _ :
For manufacturer setting
0h
_ x _ _ :
For manufacturer setting
0h
x _ _ _ :
For manufacturer setting
0h
PC24 This parameter is not used. Do not change the value.
0000h
PC24 Forced stop deceleration time constant
Set a deceleration time constant when you use the
forced stop deceleration function.
Set the time per ms from the rated speed to 0 r/min or 0
mm/s. Setting "0" will be 100 ms.
Forced stop deceleration
[Pr. PC24]
0 r/min
(0 mm/s)
Servo motor speed
(Linear servo motor
speed)
Rated speed
Dynamic brake
deceleration
[Precautions]
If the servo motor torque is saturated at the maximum
torque during forced stop deceleration because the
set time is too short, the time to stop will be longer
than the set time constant.
[AL. 50 Overload alarm 1] or [AL. 51 Overload alarm
2] may occur during forced stop deceleration,
depending on the set value.
After an alarm that leads to a forced stop deceleration,
if an alarm that does not lead to a forced stop
deceleration occurs or if the control circuit power
supply is cut, dynamic braking will start regardless of
the deceleration time constant setting.
Set a longer time than deceleration time of the
controller. If a shorter time is set, [AL. 52 Error
excessive] may occur.
100
Содержание Melservo MR-J3-100B
Страница 17: ...8 MEMO ...
Страница 18: ...Part 1 Summary of MR J3 MR J3W Replacement 1 1 Part 1 Summary of MR J3 MR J3W Replacement ...
Страница 145: ...Part 3 Review on Replacement of MR J3 _B_ with MR J4 _B_ 3 48 MEMO ...
Страница 146: ...Part 4 Replacement of MR J3W _B with MR J4W2 _B 4 1 Part 4 Review on Replacement of MR J3W _B with MR J4W2 _B ...
Страница 195: ...Part 4 Replacement of MR J3W _B with MR J4W2 _B 4 50 MEMO ...
Страница 196: ...Part 5 Review on Replacement of MR J3 DU_ with MR J4 DU_ 5 1 Part 5 Review on Replacement of MR J3 DU_ with MR J4 DU_ ...
Страница 277: ...Part 5 Review on Replacement of MR J3 DU_ with MR J4 DU_ 5 82 MEMO ...
Страница 278: ...Part 6 Common Reference Material 6 1 Part 6 Common Reference Material ...
Страница 418: ...Part 7 Review on Replacement of Motor 7 1 Part 7 Review on Replacement of Motor ...
Страница 564: ...Part 9 Startup Procedure Manual 9 1 Part 9 Startup Procedure Manual ...
Страница 567: ...Part 9 Startup Procedure Manual 9 4 MEMO ...
Страница 589: ...L NA 03127ENG C ...